10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
10.3 GOT Side Settings
*1
Cannot be set for the QCPU redundant system.
*2
For details, refer to the following manual.
Q corresponding MELSECNET/H Network System 
Reference Manual (PLC to PLC network)
(2) MELSECNET/10
POINT
POINT
POINT
(1) When MELSECNET/H communication unit is used
When connecting the MELSECNET/H network 
module to the MELSECNET/10 network system, 
specify the [MNET/10 mode] as a [Network Type].
(2) Communication interface setting by the Utility
The communication interface setting can be 
changed on the Utility's [Communication Settings] 
after writing [Communication Settings] of project 
data.
For details on the Utility, refer to the following 
manual.
GT  User's Manual
When settings are made by GT Designer3 or the 
Utility, the latest setting is effective.
10.3.3 Routing parameter setting
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be set 
twice or more (multiple times).
Therefore, the one that can access to other station from the 
request source host GOT is 64 kinds of [Transfer Network 
No.]s.
POINT
POINT
POINT
(1) Routing parameter setting
When communicating within the host network, 
routing parameter setting is unnecessary.
(2) Selection of communication unit
Routing parameters cannot be set in the GT15-
75J71LP23-Z and the GT15-75J71BR13-Z.
When setting routing parameters, use the GT15-
J71LP23-25 or the GT15-J71BR13 according to 
the connection type to be used.
For details of routing parameters, refer to the following
manual.
Q corresponding MELSECNET/H Network 
System Reference Manual (PLC to PLC 
network)
POINT
POINT
POINT
Routing parameter setting of relay station
Routing parameter setting is also necessary for the
relay station.
For the setting, refer to the following.
Refresh 
Interval
Set the number of refreshes to 
secure the send/receive data in 
station units during 
communication.
(Default: 1time)
Valid when "Secured data send/
Secured data receive" is marked 
by the control station side network 
parameters of the MELSECNET/H 
network system.
1 to 1000times
Transmission 
Speed
Set the communication 
transmission speed.
(Default: 25Mbps)
When specifying [MNET/10 mode] 
as the network type, only 10Mbps 
can be set applicable.
10Mbps/25Mbps
Item
Description
Range
Retry
Set the number of retries to be 
performed when a communication 
timeout occurs.
When no response is received after 
retries, a communication times out.
(Default: 3times)
0 to 5times
Timeout Time
Set the time period for a communication 
to time out.
(Default: 3sec)
3 to 90sec
Item
Description
Range
Item
Range
Transfer Network No.
1 to 239
Relay Network No.
1 to 239
Relay Station No.
1 to 64