FIRE TAMPER 
 
This zone type is used to monitor the wiring to bells and sirens (other than those connected to the Horn Output).  The zone will 
report trouble if an open, short, or other wiring problem is detected in the supervised bell circuit.  This zone will make a digital 
dial out when violated.  Connect a wire from the Fire Tamper zone (+) to an output configured as a Sounder. 
 
 
AUXILIARY  
 
A zone defined as AUXILIARY is ignored for security.  It is used to activate macros or to conditionalize programs.  This is the 
default setting for all zones.  Zones that are not in use should be configured as AUXILIARY. 
 
KEYSWITCH INPUT 
 
This zone is used to arm AWAY and Disarm the Omni II security system using a toggle (to ground) keyswitch or keypad. 
 
PROGRAMMABLE ENERGY SAVER MODULE  
 
This zone type is for use with the Programmable Energy Saver Modules (PESM).  It converts the Zone and the corresponding 
Output to operate the PESM.  Only Zones 9-16 can be programmed as a PESM.  
 
OUTDOOR TEMPERATURE  
 
Use this zone type for Outdoor Temperature Sensors.  The outdoor temperature can be displayed on the console, spoken over the 
telephone, or displayed on an HAI Communicating Thermostat. 
 
TEMPERATURE 
 
 
The general-purpose TEMPERATURE ZONE type is typically used to monitor indoor temperatures and control devices.  It sets 
the zone secure/not ready for program conditionals and event button activation. 
 
If FREEZE ALARM is enabled, it reports a potential freeze condition if the temperature falls below 40
o
 
TEMPERATURE ALARM  
 
The TEMPERATURE ALARM ZONE type will generate an alarm (console beeper, no sirens) and dial out if the temperature 
goes above the high setpoint or drops below the low setpoint.  
 
 
HUMIDITY 
 
The HUMIDITY ZONE type is used to monitor indoor and outdoor humidity levels from 0 to 100 percent using the Model 
31A00-2 Indoor/Outdoor Temperature and Humidity Sensor.  It sets the zone secure/not ready state for program conditionals and 
event button activation programs.
 
 
NOTE ON TEMPERATURE AND HUMIDITY ZONE TYPES
 
 
Outdoor temperature, temperature, and temperature alarm zone types all have HEAT (LOW) and COOL (HIGH) setpoints.  The 
zone is "Not Ready" when the temperature is above the high setpoint or below the low setpoint.  The zone is "Secure" when the 
temperature is between the setpoints.  Setting a setpoint to 0 disables the setpoint. 
 
Except for a type 83, the alarm is not activated.  The zone "Not Ready" or "Secure" status is used to activate button programs and 
program conditionals.