Utica Boilers SW Series II 安装指导

下载
页码 20
14
Sequence of Operation - Tankless
• Thermostat will activate, completing circuit to limit 
control.
• Circulator motor starts and power is switched to 
limit.  If limit circuit is closed burner motor circuit is 
energized.
• Burner motor starts prepurge and approximately 15 
seconds after solenoid valve opens and ignition system 
is activated, ignition will begin.
• In event boiler water temperature exceeds high limit 
setting on boiler mounted limit control; Power will be 
interrupted between limit control and ignition system. 
Burner motor will continue to run in post purge mode 
for approximately 2 min. or until water temperature 
drops below high limit setting.  Circulator will continue 
to operate under this condition until thermostat is 
satisfi ed.
• When thermostat is satisfi ed power is interrupted to 
boiler mounted limit control and burner will run in post 
purge mode for 2 minutes.
SEQUENCE OF OPERATION
ELECTRICAL WIRING
Thermostat Installation
1. 
Install thermostat on inside wall about four feet above 
fl oor.
2. 
Never install thermostat on outside wall.
3. 
Do not install thermostat where it will be affected by:
A. Drafts
B.  Hot or cold pipes
C. Sun light
D. Lighting fi xtures
E. Television sets
F. A 
fi replace or chimney
4. 
Check thermostat operation by raising and lowering 
thermostat as required to start and stop burner.
5. 
Instructions for fi nal adjustment of thermostat 
are packaged with thermostat  (adjusting heating 
anticipator, calibration, ect.).
Sequence of Operation - Non-Tankless
• Thermostat calls for heat.
• Circulator turns on.
• Limit checks boiler water temperature. Burner ignition 
delayed until limit determines call for heat cannot be met 
by residual heat in boiler and heat distribution system. 
See limit literature for additional information.
• Burner and circulator operation continues until 
thermostat stops call for heat.