Venting system should be inspected at start of each heating
season.
• Check vent pipe from boiler to termination cap for
signs of deterioration by rust or cracked silicone joints.
Repair if necessary.
• Lever of safety relief valve, shown in Figure 17, on
page 18, on boiler should be operated periodically to
make sure it is functioning properly. Pressure relief
valve should open before water pressure exceeds
30 psi. reading on gauge. If pressure is exceeded
and pressure relief valve leaks water when boiler is
operating at normal pressures, immediately replace.
Corrosion can build up rapidly at valve seat preventing
it functioning as safety device.
Start-up and adjustment of oil burner (See oil burner
instructions for nozzle and electrode setting).
A. Check oil burner nozzle to make certain it is tight in
adapter. Burner mounting bolts should be tight.
B. Check electrode setting, as they may have been
jarred out of position during transportation.
C. Lubricate burner motor and circulator motor if
required. Some circulators are water lubricated and
do not require oiling.
D. Set room thermostat to call for heat.
E. Open all oil line valves.
F. Turn service switch on. Burner should start.
G. On one pipe fuel systems only, vent pump as soon
E. Open all oil line valves.
F. Turn service switch on. Burner should start.
G. On one pipe fuel systems only, vent pump as soon
as burner starts. Allow oil to run until all traces of
air in the suction line disappear.
H. Turn “OFF” burner and install pressure gauge in
port on pump.
I. Start burner again and check oil pressure for 140
psi. Adjust if necessary.
OPERATING INSTRUCTIONS
Instruments are only reliable method to determine proper
air adjustments. Improperly adjusted burner causes soot
and high fuel bills because of incomplete combustion of fuel
oil. This in turn may require excessive boiler maintenance,
service costs. Consult competent service mechanic to make
proper adjustments with smoke tester, CO
2
indicator and
draft gauge. Bacharach or Dwyer test kits include these
instruments.
• 1/4" diameter slot is provided in inspection cover plate
to take draft reading in combustion chamber.
• 3/8" hole is provided in vent appliance adapter to take
draft, CO
2
, smoke, and temperature readings.
• Adjust air dial on oil burner to obtain trace of smoke.
Measure CO
2
at this point and increase air setting until
CO
2
= 1-1.5% lower than reading at trace point.
• Check draft over fi re and in vent, normal readings will
be positive (+.01 Over-fi re & +.02 In Vent) W.C.
Table page 17 is provided as guideline for initial start-
up. Final adjustments MUST be made using combustion
instruments as previously mentioned.