Failsafe Upgrade Feature 
 
160
 
 
 
STEP 1: Update the Main Unit's boot loader to 0C4 and firmware to 
3E5 or later 
There are two types of scenarios: 
•  The boot loader version of the Main Unit is earlier than 0C4—you 
must upgrade its boot loader to 0C4 or later. See Updating Main 
Units for Failsafe Upgrade Feature
 in Main Units (on page 157) for 
details. 
•  The boot loader version of the Main Unit is 0C4 or later, but its 
firmware code is earlier than 3E5—download the firmware of version 
4.2 or later, and upgrade it by following the procedure described in 
General Update Procedure (on page 153). The firmware file to choose 
is P2‐xxx.hex (xxx represents the version). 
STEP 2: Keep only one Stacking Unit connected 
To upgrade the Stacking Unit for obtaining the failsafe capability, only 
one unit is allowed to connect to the Main Unit at one time. If there are 
more than one Stacking Unit or no Stacking Unit connected to the Main 
Unit, you must do the following: 
1.  Power off the Main and Stacking Units. 
2.  Connect only one Stacking Unit to the Main Unit. 
3.  Power on the Stacking Unit first. 
4.  Power on the Main Unit. 
5.  Set the Main Unitʹs stacking support to 1. See the “Stacking Support” 
section under Paragon II Front Panel Display and Controls (on page 
16) for additional information. 
6.  Set the Stacking Unit ID to 1. See step 6 of Installing the Paragon 
P2‐UMT1664S Stacking Unit (on page 35) for additional information. 
7.  Power off both units. 
8.  Power on the Stacking Unit first. 
9.  Power on the Main Unit. 
STEP 3: Update the Stacking Unit's firmware 
Both of the Stacking Unitʹs firmware code and boot loader will be 
updated after the following is done. 
1.  Make sure the Main Unit is connected, via network, to the PC that 
will run Paragon Update. 
2.  Launch the Paragon Update utility: select “R‐P2SBL‐0C5.hex” as the 
firmware file, and click the “Send To Paragon” button. See Paragon 
Manager User Guide
 for detailed operation.