Trane Gas Unit Heaters Wartungshandbuch

Seite von 53
Maintenance
GTND-SVX01B-EN
45 
close tightly, completely extinguishing the flame on 
the main burner(s).
12. Inspect and service the motor/fan assemblies. To 
maintain efficient air flow, inspect and clean the fan 
blades and guard to prevent buildup of foreign matter.
13. Check lubrication instructions on the motor. If oiling is 
required, add 3 to 4 drops of electric motor oil as 
follows:
a. Light Duty—After 3 years or 25,000 hours of 
operation.
b. Average Duty—Annually after 3 years or 
8,000 hours of operation.
c. Heavy Duty—Annually after 1 year or at least 
1,500 hours of operation.
14. Check and test the operational functions of all safety 
devices supplied with your unit.
How to Order Replacement Parts
Please send the following information to your local Parts 
center; If further assistance is needed, contact the 
manufacturer’s customer service department.
Model  number
Serial Number
Part description and Number as shown in the 
Replacement Parts Catalog.