Issue 10/06   
3  Factory setting 
MICROMASTER 440   
Operating Instructions (Compact) 
23
 
3 Factory 
setting 
The MICROMASTER 440 frequency inverter is set in the factory so that it can be 
operated without any additional parameterization. To do this, the motor parameters 
set in the factory (P0304, P0305, P0307, P0310), that correspond to a 4-pole 1LA7 
Siemens motor, must match the rated data of the connected motor (refer to the 
rating plate). 
Further factory setting:
 
¾
  Command sources  P0700 = 2 (Digital input, see Fig. 3-1) 
¾
  Setpoint source  
P1000 = 2 (Analog input, see Fig. 3-1) 
Analog output
¾
 Motor cooling 
P0335 = 0 
¾
  Motor current limit  
P0640 = 150 % 
¾
  Min. frequency  
P1080 = 0 Hz 
¾
 Max. frequency 
P1082 = 50 Hz 
¾
 Ramp-up time 
 
P1120 = 10 s 
¾
 Ramp-down time 
 
P1121 = 10 s 
¾
 Control mode 
 
P1300 = 0 
Fig. 3-1 
Pre-assignment of the inputs 
Input/Output Terminals 
Parameter 
Function 
Digital input 1 
P0701 = 1 
ON / OFF1 
(I/O) 
Digital input 2 
P0702 = 12 
Reversing 
(
Digital input 3 
P0703 = 9 
Fault acknowledge 
(Ack) 
Digital input 4 
P0704 = 15 
Fault acknowledge 
Digital input 5 
16 
P0705 = 15 
Fixed setpoint (direct) 
Digital input 6 
17 
P0706 = 15 
Fixed setpoint (direct) 
Digital input 7 
Via ADC1  P0707 = 0 
Fixed setpoint (direct) 
Digital input 8 
Via ADC2  P0708 = 0 
Digital input disabled 
 
3.1 
50/60 Hz DIP switch 
The default motor base frequency 
of the MICROMASTER inverter is 
50 Hz. For motors, which are 
designed for a base frequency of 
60 Hz, the inverters can be set to 
this frequency using the DIP50/60 
switch. 
¾
  OFF position:  
European defaults (Rated 
motor frequency = 50 Hz, 
Power in kW etc.) 
¾
 ON position:  
North American defaults  
(Rated motor frequency = 60 Hz, Power in hp etc.) 