4  Communications 
Issue 10/06 
 
MICROMASTER 440 
24 
Operating Instructions (Compact) 
4 Communications 
4.1 Establishing 
communications 
MICROMASTER 440 
 STARTER 
The following optional components are additionally required in order to establish 
communications between STARTER and MICROMASTER 440: 
¾
  PC <-> frequency inverter connecting set 
¾
  BOP if the USS standard values (refer to Section 6.4.1 "Serial Interface (USS)") 
are changed in the MICROMASTER 440 frequency inverter 
PC <-> frequency inverter connecting set 
MICROMASTER 440 
USS settings, refer to 6.4.1 "Serial 
Interface (USS)"  
STARTER 
Menu, Options --> Set PG/PC interface 
--> Select "PC COM-Port (USS)" --> 
Properties --> Interface "COM1", select 
a baud rate 
 
 
NOTE 
The USS parameter settings in the 
MICROMASTER 440 frequency inverter 
and the settings in STARTER must 
match! 
 
4.2 Establishing 
communications 
MICROMASTER 440 
 AOP 
¾
  Communications between AOP and MM440 are based on the USS protocol, 
analog to STARTER and MM440.  
¾
  Contrary to the BOP, the appropriate communication parameters - both for the 
MM440 as well as for AOP - should be set if the automatic interface detection 
was not carried-out (refer to Table 4-1). 
¾
  Using the optional components, the AOP can be connected to the 
communication interfaces (refer to Table 4-1). 
Table 4-1 
 
AOP at the BOP link 
AOP at the COM link 
MM440 parameters 
- baud rate 
- bus address 
 
P2010[1] 
– 
 
P2010[0] 
P2011 
AOP parameters 
- baud rate 
- bus address 
 
P8553 
– 
 
P8553 
P8552 
Options 
- direct connection 
- indirect connection 
 
No option necessary 
BOP/AOP door mounting kit
(6SE6400-0PM00-0AA0) 
 
Not possible 
AOP door mounting kit 
(6SE6400-0MD00-0AA0)