4  Communications 
MICROMASTER 440   
Operating Instructions (Compact) 
25
 
AOP as control unit 
Parameter / Terminal 
AOP on BOP link  
AOP on COM link 
Command source 
 / 
 
P0700 4 
P1000 1 
P1035 
2032.13 (2032.D) 
2036.13 (2036.D) 
P1036 
2032.14 (2032.E) 
2036.14 (2036.E) 
 
 
Frequency setpoint 
(MOP) 
 
 
 
 
Output frequency of the MOP higher 
 
 
Output frequency of the MOP lower 
Acknowledge fault 
 
P2104 2032.7 
2036.7 
 
• A fault can be acknowledged via the AOP independently of P0700 or P1000. 
 
4.3 
Bus interface (CB) 
DeviceNet
P0918
CANopen
P0918
PROFIBUS
P0918 *)
Bus interface (CB)
P2040
P2040
P2040
P2041
P2041
P2041
P2051
P2051
P2051
Baud rate is
automatically specified
by the master
 
 
*) DIP switch for addressing the hardware must be observed 
 DeviceNet 
CANopen 
PROFIBUS 
P2041[0] 
PZD length 
Status/actual value 
Data transfer type 
from T_PD0_1, T_PD0_5 
P2041[1] 
PZD length 
control/setpoint 
Data transfer type  T_PD0_6 
 R_PD0_1 
 R_PD0_5 
 R_PD0_6 
P2041[2] 
Baud rate 
0: 125 kbaud 
 
1: 250 kbaud 
 
2: 500 kbaud 
Mapping CANopen <--> MM4 
P2041[3] 
Diagnostics 
Mapping CANopen <--> MM4 
P2041[4] _ 
- response to communication errors 
- baud rate 
Setting is not 
required (only in 
special cases). 
Refer to the 
Operating 
Instructions 
"PROFIBUS 
option module"