Siemens 440 User Manual

Page of 78
5  BOP / AOP (Option) 
Issue 10/06 
 
MICROMASTER 440 
26 
Operating Instructions (Compact) 
BOP / AOP (Option) 
Buttons and their Functions 
Panel/ 
Button 
Function Effects 
 
Indicates 
Status 
The LCD displays the settings currently used by the converter.
 
  
Start 
converter 
Pressing the button starts the converter. This button is disabled by default. 
Activate the button:
 
BOP:
  P0700 = 1 or P0719 = 10 ... 16 
AOP:  P0700 = 4 or P0719 = 40 ... 46
 
on BOP link 
 
 
P0700 = 5 or P0719 = 50 ... 56
  
on COM link 
 
Stop 
converter 
OFF1  Pressing the button causes the motor to come to a standstill at the 
selected ramp down rate.  
Activate the button: see button "Start converter"
 
OFF2  Pressing the button twice (or once long) causes the motor to coast 
to a standstill.  
   BOP: 
This function is always enabled 
 
(independent of P0700 or P0719). 
 
Change 
direction 
Press this button to change the direction of rotation of the motor. Reverse is 
indicated by a minus (-) sign or a flashing decimal point. Disabled by default. 
Activate the button: see button "Start converter".
 
 
Jog motor 
In the "Ready to power-on" state, when this key is pressed, the motor starts 
and rotates with the pre-set jog frequency. The motor stops when the button 
is released. Pressing this button when the motor is running has no effect. 
 
Functions 
This button can be used to view additional information. 
It works by pressing and holding the button. It shows the following, starting 
from any parameter during operation: 
1.  DC link voltage (indicated by d – units V). 
2.  output current. (A) 
3.  output frequency (Hz) 
4.  output voltage (indicated by o – units V). 
5.  The value selected in P0005 (If P0005 is set to show any of the above 
(1 - 4) then this will not be shown again).  
Additional presses will toggle around the above displays. 
Jump Function 
From any parameter (rxxxx or Pxxxx) a short press of the Fn button will 
immediately jump to r0000, you can then change another parameter, if 
required. Upon returning to r0000, pressing the Fn button will return you to 
your starting point. 
Acknowledgement 
If alarm and fault messages are present, then these can be acknowledged by 
pressing key Fn. 
 
Access 
parameters 
Pressing this button allows access to the parameters. 
 
Increase 
value 
Pressing this button increases the displayed value. 
 
Decrease 
value 
Pressing this button decreases the displayed value. 
+
 
AOP menu  Calls the AOP menu prompting  (this is only available for AOP).