Toshiba HCV-1JBU Instruction Manual

Page of 30
 
Page 18 
 
MAINTENANCE 
 
 
 
Table 2 - Check Points for Periodic Inspection 
Check 
Point 
Check Item 
Check Method 
Criteria 
Disposition 
Operating 
Mechanism 
Loose bolts, 
nuts or 
screws 
Tighten using 
screwdriver or 
wrench. 
Make sure all bolts, 
nuts and screws are 
tight. 
Tighten if loose.  
See Table 1 for 
tightening torque 
specifications. 
 
Dust or 
foreign 
matter inside 
Visual inspection. 
The contactor should be 
clean and contain no 
foreign matter. 
Wipe with a clean 
dry cloth. 
 
Electro-
magnets 
Visual inspection. 
Check for rust, 
discoloration, wear, or 
loose mountings. 
Wipe with a clean 
dry cloth. 
 
Closing coil 
Visual inspection. 
Check for discoloration, 
and burned parts. 
Wipe with a clean 
dry cloth. 
 
Spring 
Visual inspection. 
Check for rust, 
deformation, 
discoloration, or 
damage. 
Wipe with clean dry 
cloth.  Lubricate if 
necessary. 
 
Smooth 
operation 
Visual inspection or 
touch.  Check 
lubrication. 
Make sure moving parts 
operate smoothly. 
Apply a small 
amount of 
lubrication. 
Main Circuit  Terminals 
and movable 
conductors. 
Visual inspection.  
Tighten using 
screwdriver or 
wrench. 
Make sure there is no 
discoloration or loose 
fasteners. 
Check the cause 
and repair.  Tighten 
connections to 
contactor.  See 
(Table 1) for 
tightening torque 
specifications. 
 
Loose bolts, 
nuts or 
screws 
Tighten using a 
wrench. 
Make sure all bolts, 
nuts and screws are 
tight. 
See Table 1 for 
tightening torque 
specifications. 
 
Vacuum 
contact wear. 
See Electrical 
Service Life (Page 
23). 
Check contact wear and 
wipe. 
Replace vacuum 
interrupter. 
 
Vacuum 
level. 
Apply 10kV AC for 1 
minute. 
Check vacuum level by 
withstand voltage test. 
If breakdown occurs, 
contact Toshiba. 