MAINTENANCE 
 
Page 19 
 
 
 
Table 2 – Check Points for Periodic Inspection (cont.) 
Check 
Point 
Check Item 
Check Method 
Criteria 
What to do 
Main Circuit  Dust on 
surface of 
vacuum 
interrupter 
Visual inspection. 
Make sure there is no 
dust on the surface. 
Wipe with a clean, 
dry cloth. 
Insulation 
Frame and 
Flanges 
Dust, foreign 
matter or 
damage 
Visual inspection. 
Make sure there is no 
dust, foreign matter or 
breakage. 
Wipe with a clean, 
dry cloth.  If 
damaged, contact 
Toshiba. 
Control 
Circuits 
Auxiliary 
Switch 
See Table 3. 
Contact wear and wipe. 
Make sure there is no 
dust. 
Replace if wear or 
damage is 
excessive. See 
Table 1 for 
tightening torque 
specifications 
 
Drive unit 
Visual inspection. 
Check for overheating 
and discoloration. 
Replace if damaged.
 
Wiring 
Visual inspection.  
Tighten using a 
screwdriver. 
Check for discoloration 
and tightness. 
Repair if 
disconnected.  
Tighten if loose.  
See Table 1 for 
tightening torque 
specifications. 
Insulation 
Resistance 
Measure-
ment 
Resistance 
from main 
circuit to 
ground 
Measure insulation 
resistance between 
phases, between 
electrodes, and 
between circuits and 
ground.  Megger test 
at 1000V. 
Resistance should be 
50MΩ or greater. 
 
Resistance 
from control 
circuits to 
ground 
Measure insulation 
resistance between 
circuits and ground.  
Megger test at 
500V. 
Resistance should be 
1MΩ or greater. 
If the insulation 
resistance is low, 
wipe off the vacuum 
interrupter and other 
insulation surfaces 
with a clean dry 
cloth and then 
repeat the test.  If 
necessary, replace 
faulty parts. 
 
 