Motor Setup Guidelines 
77 
Setting Up DC Brush Motor 
Before you start 
 
It is always recommended to start a fresh setup from factory default settings, $$$*** 
followed by a Save and a $$$. 
 
Don’t forget to create/edit the motor type and protection power-on PLC 
 
At this point of the setup it is assumed that the encoder has been wired and configured 
correctly in the Encoder Feedback section. And that moving the motor/encoder shaft by 
hand shows encoder counts in the position window.  
 
Parameters with Comments ending with -User Input require the user to enter information 
pertaining to their system/hardware. 
 
Downloading and using the suggested M-variables is highly recommended.   
 
Detailed description of motor setup parameters can be found in the 
 
Phasing Search Error Bit, Current-Loop Integrator Output 
On power-up, the phasing search error bit has to be cleared to allow motor move commands to 
DC Brush motor. This can be added to the power-on PLC. Also, the current-loop integrator 
output should not be allowed to build up over time. The motor (non-existent) direct current-loop 
output should be zero-ed periodically. 
M148->Y:$C0,8,1 
; Motor 1 Phasing error fault bit 
M248->Y:$140,8,1 
; Motor 2 Phasing error fault bit 
M348->Y:$1C0,8,1 
; Motor 3 Phasing error fault bit 
M448->Y:$240,8,1 
; Motor 4 Phasing error fault bit 
M601->Y:$BC,0,24,U 
; Motor 1 Direct Current-Loop Integrator Output 
M602->Y:$13C,0,24,U 
; Motor 2 Direct Current-Loop Integrator Output 
M603->Y:$1BC,0,24,U 
; Motor 3 Direct Current-Loop Integrator Output 
M604->Y:$23C,0,24,U 
; Motor 4 Direct Current-Loop Integrator Output 
Open plc 2 clear 
If (M148=1) 
 
 
 
 
 CMD"M148,4,100=0" 
 
; Clear Phasing Error Bit 
EndIF 
M601=0 M602=0 M603=0 M604=0 
; Zero Current-Loop Integrator Output  
Close   
 
 
; This PLC has to be active always  
 
Flag Control, Commutation Enable, Phase Angle, Current Mask: Ixx24, 
Ixx01, Ixx72, Ixx84 
I124,4,100=$800001 
; Motors 1-4 Flag control, High true amp fault (Turbo Clipper Drive 
specific)   
I101,4,100=1 
 
; Motors 1-4 Commutation enabled 
I172,4,100=512  
; Motors 1-4 Commutation phase angle (Turbo Clipper Drive specific)  
I184,4,100=$FFFC00 
; Motors 1-4 Current-Loop Feedback Mask Word(Turbo Clipper Drive specific)