Delta Tau GEO BRICK LV Reference Manual

Page of 760
Turbo PMAC/PMAC2 Software Reference
 
Turbo PMAC On-line Command Specification 
 373 
MACROSLVWRITE 
Function: 
Write (copy) Type 1 MACRO auxiliary parameter value  
Scope:   
Global 
Syntax:  
MACROSLVWRITE{node #},{slave variable},{PMAC variable} 
MSW{node #},{slave variable},{PMAC variable} 
where: 
 
{node #} is a constant in the range 0 to 63 representing the number of the node on the Turbo 
PMAC matching the slave node to be accessed, where the node number specification is: 
 
{node #} = 0 – 15 specifies MACRO IC 0 nodes 0 – 15, which correspond to slave nodes 0 – 
15 of the same master number as MACRO IC 0; 
 
{node #} = 16 – 31 specifies MACRO IC 1 (Ultralites with Option 1A only) nodes 0 – 15, 
which correspond to slave nodes 0 – 15 of the same master number as MACRO IC 1; 
 
{node #} = 32 – 47 specifies MACRO IC 2 (Ultralites with Option 1B only) nodes 0 – 15, 
which correspond to slave nodes 0 – 15 of the same master number as MACRO IC 2; 
 
{node #} = 48 – 63 specifies MACRO IC 3 (Ultralites with Option 1C only) nodes 0 – 15, 
which correspond to slave nodes 0 – 15 of the same master number as MACRO IC 3; 
 
{slave variable} is the name of the MI-variable or C-command on the slave station whose 
value is to be set; 
 
{PMAC variable} is the name of the variable on the PMAC from which the value of the slave 
station variable is to be copied 
This command causes Turbo PMAC to copy the value of the specified variable on Turbo PMAC to the 
specified variable of the MACRO slave station matching the specified node number on the Turbo PMAC, 
using the MACRO Type 1 master-to-slave auxiliary protocol.  If the slave station variable is not node-
specific, {node #} can represent the number of any active node on the slave station.  
The variable on the Turbo PMAC can be any of the I, P, Q, or M-variables on the card. 
If this command is issued to the Turbo PMAC while a PLC buffer is open, it will be stored in the buffer 
as a PLC command, not executed as an on-line command. 
In order for the Turbo PMAC to be able to execute this command, the following conditions must be true: 
 
The MACRO IC used must be set up as a master or the synchronizing ring master 
(I6840/6890/6940/6990 = $xx90 or $xx30); 
 
MACRO IC 0 node 15 auxiliary register copy function must be disabled (I70 bit 15 = 0); 
 
MACRO IC 0 node 15 must not be used for any other function. 
If the slave node returns an error message or it does not respond within I78 servo cycles, Turbo PMAC 
will report ERR008.  Bit 5 of global status register X:$000006 is set to report such a MACRO auxiliary 
communications error.  Register X:$0031EE holds the error value.  It is set to $010000 for a timeout 
error, or $xxxxFE if the slave node reports an error, where xxxx is the 16-bit error code reported by the 
slave node. 
Examples: 
MSW0,MI910,P35 
; Copies value of PMAC P35 into MACRO station node 0 variable MI910 
MSW4,C4,P0 
; Causes MACRO station with active node 4 to execute Command #4, saving its 
 
; setup variable values to non-volatile memory (P0 is a dummy variable here)