Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
PinOuts and Software Setup 
 109 
Absolute Power-On Position Read (Technique 2) 
With technique 2, the absolute power-on position can be read directly from the serial data registers. But, 
proper scaling (5-bit right shift, in a PLC) is required to conform to the unshifted on-going position. 
 
Example 1: Channel 1 driving a 37-bit (25-bit single turn, 12-bit multi-turn) rotary serial encoder: 
I180=0   
 
 
; Absolute power-on read disabled 
I110=$78B20 
 
 
; Absolute power-on position address (ch1 serial data register A) 
I195=$A50000 
 
 
; Parallel Read, 37 bits, Signed, from Y-Register –User Input 
 
Bit 23: =1 Signed
      
    =0 Unsigned
1 0 1 0 0 1 0 1
Bit 22: =1 X-Register
            =0 Y-Register
Bits16-21: Number of Bits to read
(Resolution 37 bits or 100101 )
Ixx95
Binary:
Hex($):
A
5
0 0 0 0 0 0 0 0
0
0
0 0 0 0 0 0 0 0
0
0
Bits 0-15: reserved
(always 0)
 
In this mode, PMAC reads 37 bits from the consecutive serial data registers: 
Serial Register A
(Ch1 Y:$78B20)
Serial Register B
(Ch1 Y:$78B21)
37 bits
0
23
47
 
With  the  setting  of  Ixx80=0,  the  actual  position  is  not  reported  automatically  on  power-up.  It  will  be 
reported after scaling (i.e. in PLC, below).  
 
Example 2: Channel 1 driving a 25-bit (25-bit Singleturn, No Multiturn) absolute rotary serial  encoder, 
or a similar protocol resolution (25 bits) linear scale: 
I180=0   
 
 
; Absolute power-on read disabled 
I110=$78B20 
 
 
; Absolute power-on position address (ch1 serial data register A) 
I195=$190000 
 
 
; Parallel Read, 25 bits, Unsigned, from Y-Register –User Input 
 
Bit 23: =1 Signed
      
    =0 Unsigned
0 0 0 1 1 0 0 1
Bit 22: =1 X-Register
            =0 Y-Register
Bits16-21: Number of Bits to read
(Resolution 25 bits or 011001 )
Ixx95
Binary:
Hex($):
1
9
0 0 0 0 0 0 0 0
0
0
0 0 0 0 0 0 0 0
0
0
Bits 0-15: reserved
(always 0)
 
In this mode, PMAC reads 25 bits from the first serial data register: 
Serial Data Register A
(Ch1 Y:$78B20)
Serial Data Register B
(Ch1 Y:$78B21)
25 bits
0
23
47
 
With  the  setting  of  Ixx80=0,  the  actual  position  is  not  reported  automatically  on  power-up.  It  will  be 
reported after scaling (i.e. in PLC, below).