Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
PinOuts and Software Setup 
 25 
Disabling the STO 
Disabling the STO maintains full backward compatibility with existing systems, 
pre-STO installations. This can be simply done by tying STO disable (pin #4) to 
STO Disable RTN (pin #5). 
 
Pins 1, 2 and 3 have no practical use in this mode, and should be left floating. 
STO Out
TB3
STO IN 1
STO IN 2
STO DISABLE
STO DISABLE RTN
5
4
3
2
1
 
 
Wiring and Using the STO 
Single STO Trigger 
Dual STO Trigger(s) 
STO Out
TB3
STO IN 1
STO IN 2
STO DISABLE
STO DISABLE RTN
5
4
3
2
1
24 VDC
Power Supply
COM
+24 VDC
N.C
Input to Brick/Logic
2
3
1
+ 24VDC
CHGND
+24VRET
TB1
 
STO Out
TB3
STO IN 1
STO IN 2
STO DISABLE
STO DISABLE RTN
5
4
3
2
1
24 VDC
Power Supply
COM
+24 VDC
N.C
Input to Brick/Logic
2
3
1
+ 24VDC
CHGND
+24VRET
TB1
 
 
In  normal  mode  operation,  the  STO  relay(s)  must  be  normally  closed.  +24VDC  must  be  applied  to 
both STO inputs (pins #2, #3) to allow power to the motors. 
 
 
The STO is triggered, and power is  disconnected from the motors, if the +24V is disconnected from 
either STO inputs (pins #2, #3). 
 
 
The  STO  Out  (pin  #1)  is  a  voltage  status  output  rated  to  24  VDC 
±10%  at  a  max  of  125mA
.  It 
reflects the status of the STO function: 
  (24 V) in normal mode operation (+24VDC connected to both STO inputs) 
  ( 0  V) in triggered mode (+24VDC disconnected from either STO inputs) 
 
 
Certain safety standards require dual protection, thus mandating the use of two STO input triggers. 
 
 
The  STO  relay(s)  can  be  wired  in  series  with  the  E-Stop  circuitry  which  typically  disconnects  the 
main bus power from the system. 
 
Summary of operation and status: 
+24 VDC 
STO State 
STO Out 
Applied to both STO Inputs 
Not Triggered (normal mode operation) 
24V 
Disconnected from either STO inputs 
Triggered 
0V