Setting up Quadrature Encoders 
Digital Quadrature Encoders use the 1/T incremental entry in the  encoder conversion table. Position and 
velocity pointers should, by  default, be  valid and in  most cases  no software setup  is required, activating 
(Ixx00=1) the corresponding channel is sufficient to see encoder counts in the position window when the 
motor/encoder shaft is moved by hand. 
 
I100,8,100=1 
; Channels 1-8 activated   
 
Encoder Count Error (Mxx18) 
The  Geo  Brick  LV  has  an  encoder  count  error  detection  feature.  If  both  the  A  and  B  channels  of  the 
quadrature encoder change state at the decode circuitry (post-filter) in the same hardware sampling clock 
(SCLK) cycle, an unrecoverable error to the counter value will result (lost counts). Suggested M-Variable 
Mxx18 for this channel is then set and latched to 1 (until reset or cleared). The three most common root 
causes of this error: 
 
Real encoder hardware problem 
 
Trying to move the encoder (motor) faster than it’s specification 
 
Using an extremely high resolution/speed encoder. This may require increasing the SCLK   
The default sampling clock in the Geo Brick LV is ~ 10MHz, which is acceptable for virtually all 
applications. A setting of I7m03 of 2257 (from default of 2258) sets the sampling clock SCLK at about 
~20MHz. It can be increased to up to ~40 MHz. 
 
 
Note 
No automatic action is taken by the Geo Brick LV if the encoder count 
error bit is set.