HE420A STEAM POWER HUMIDIFIER
5
69-1108—2
Installing the Humidistat to Operate 
Manually
1. Locate the three-pin arrangement marked AUTO/
MAN protruding from the control board (right of wir-
ing connections).
2. Pull upward to remove the black, two-pin connector 
from the auto position. Reinstall it in the manual 
position (on the center and right-hand pins).
CAUTION
Do not attach sensor wire to the blue wiring 
connection block.
3. Follow Steps 8 (select a power source) and 9 (Con-
nect the humidistat to the humidifier) to complete 
the wiring. Apply the manual mode faceplate to the 
compensating humidistat cover. Reattach the cover 
to the base and reinstall the knob.
HUMIDISTAT OPERATING 
INSTRUCTIONS
With automatic humidity control, you can control your 
humidifier almost effortlessly, because: 
• Once the knob has been set, the humidistat 
automatically adjusts the indoor relative humidity 
based on outdoor temperature and your desired 
humidity level.
• The humidistat calculates the optimal humidity so you 
don't have the problems associated with indoor 
condensation.
• The humidistat’s temperature condensation capability 
automatically turns itself on in cold weather, off in 
warm weather.
• The humidistat’s humidity and temperature sensors 
are solid-state, which means there are no mechanical 
parts, and no problems associated with dust.
Automatic Operation
Once the humidistat is installed in the cold air return and 
internally set to AUTOMATIC, turn the dial to 5 (the 
standard humidity control setting).
Allow the humidity to stabilize for at least two days (home 
size, furnace efficiency, and personal comfort preference 
may affect the length of time necessary). At that point, you 
may reset the dial to 6 for more humidity, or 4 for less 
humidity. Continue adjusting the dial until you reach your 
optimal indoor humidity level, and leave the dial in this 
position.
Remember that in AUTO mode, the dial is not showing 
relative humidity, but your preferred humidity setting 
based on Table 1.
Manual Operation
For MANUAL operation, apply the manual mode decal to 
the faceplate. Once the unit is installed in the cold air 
return and internally set to MANUAL, turn the dial to the 
expected outdoor temperature. The corresponding 
optimal humidity level has been calibrated for you. For 
example, by setting the dial to an anticipated 20°F, the 
humidistat automatically maintains the indoor relative 
humidity in the safe, comfortable 35% range (see Table 2 
below).
In extreme cold weather, relative humidity must be 
reduced to prevent condensation on windows and interior 
surfaces. Otherwise, the excess moisture will eventually 
cause damage to your home.
Additional Features
• When outdoor temperature exceeds 50°F (10°C), the 
humidistat will function in Test mode only.
• When indoor relative humidity exceeds 45%, the 
humidistat will not operate.
• Test Mode—Manual test the humidistat by turning the 
knob to the far right. The unit will energize the internal 
relay for one minute, allowing you to confirm proper 
operation.
• Manual Off—In Manual mode, turn the humidistat OFF 
during warm months by turning the knob to the far left. 
(This is not necessary in Automatic mode.)
HUMIDISTAT CHECKOUT
IMPORTANT
If conditions exceed 50°F or 45 percent relative 
humidity, it may be necessary to perform this 
test.
1. To conduct a system test, ensure that 24 VAC is 
applied to the 24 VAC terminals of the compensat-
ing humidistat.
2. Reattach the humidistat cover and knob to the 
base.
3. Rotate the knob on the humidistat clockwise to the 
“Test” position.
Table 1. Humidity Settings.
Dial 
Position
Outdoor Temperature °F
-10
0
10
20
30
40
1
10%
10%
10%
15%
20%
25%
2
10%
10%
15%
20%
25%
30%
3
10%
15%
20%
25%
30%
35%
4
15%
20%
25%
30%
35%
40%
5
20%
25%
30%
35%
40%
45%
6
25%
30%
35%
40%
45%
45%
7
30%
35%
40%
45%
45%
45%
Table 2. Recommended Relative Humidity.
Outside Temperature
Recommended RH
+40°F
45%
+30°F
40%
+20°F
35%
+10°F
30%
0°F
25%
-10°F
20%
-20°F
15%
Table 1. Humidity Settings.
Dial 
Position
Outdoor Temperature °F
-10
0
10
20
30
40