Goodman Mfg SS-CPC90-150 Benutzerhandbuch

Seite von 36
p
rodUCt
 s
peCifiCations
p
rodUCt
 s
peCifiCations
SS-CPC90-150
  
www.goodmanmfg.com 
3
p
rodUCt
 s
peCifiCations
 — 7½ t
ons
A Models
B Models
CPC090 
XXX3BXXX
CPC090 
XXX4BXXX
CPC090 
XXX3BXXX
CPC090 
XXX4BXXX
CPC090 
XXX7BXXX
Cooling Capacity
Total BTU/h
90,000
90,000
90,000
90,000
90,000
Sensible BTU/h
65,700
65,700
64,000
64,000
64,000
EER / IEER
11.5 / 11.5
11.5 / 11.5
11.5 / 11.5
11.5 / 11.5
11.5 / 11.5
Decibels
82.0
82.0
82.0
82.0
82.0
AHRI Reference #s
3000986
3000986
3620223
3620223
3620223
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
3,000
3,000
3,000
3,000
3,000
Indoor Motor FLA (Cooling)
7.8
3.9
5.0
2.5
2.3
Horsepower / RPM
2.0 / 1725
2.0 / 1725
1.5 / 1745
1.5 / 1745
1.5 / 1725
Piston Size (Cooling)
0.076
0.076
0.078
0.078
0.078
Filter Size (Qty)
(4) 16”x24”x2”
(4) 16”x24”x2”
(4) 16”x20”x2”
(4) 16”x20”x2”
(4) 16”x20”x2”
Drain Size (NPT)
¾”
¾”
¾”
¾”
¾”
R-410A Refrigerant Charge  Cir #1 & #2
215 oz.
215 oz.
175 oz.
175 oz.
175 oz.
Evaporator Coil Face Area (ft²)
10.2
10.2
8.9
8.9
8.9
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1  (15” x 12”)
1  (15” x 12”)
1  (15” x 12”)
1  (15” x 12”)
1  (15” x 12”)
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt 
AX51
AX51
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
2
Horsepower - RPM
¼ - 1090
¼ - 890
¼ - 1075
¼ - 890
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
7,600
7,600
7,600
7,600
7,600
Face Area (ft²)
32.4
32.4
26.5
26.5
26.5
Rows Deep / Fins per Inch
2 / 20
2 / 20
2 / 22
2 / 22
2 / 22
Compressor
Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
Stage
1
1
1
1
1
Electrical Data
Voltage-Phase-Frequency
208/230-3-60
460-3-60
208/230-3-60
460-3-60
575-3-60
Quantity of Compressors 
2
2
2
2
2
Compressor RLA  / LRA 
13.1 / 83.1
6.1 / 41.0
13.1 / 83.1
6.1 / 41.0
4.4 / 33.0
Max External Static
1.5”
1.5”
1.0”
1.0”
1.0”
Outdoor Fan HP / RLA
(2) ¼ / 1.4
(2) ¼ / 0.8
(2) ¼ / 1.4
(2) ¼ / 0.8
(2) ¼ / 0.6
Total Unit Amps
36.9
17.7
34.0
16.3
12.3
Min. Circuit Ampacity¹
40
19
37.3
17.8
13.4
Max. Overcurrent Protection (amps)²
50
25
50
20
15
Entrance Power Supply
Locating 
Dimple
Locating 
Dimple
Locating 
Dimple
Locating 
Dimple
Locating 
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1110
1110
975
975
975
Ship Weight (lbs)
1150
1150
1000
1000
1000
¹  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.