Magnetek TM7310rev01 Benutzerhandbuch

Seite von 126
Quattro DC Motor A6 Submenu 
 
48
 
 
Parameter Description 
Units 
Default
Range 
Hidden
Item 
Run 
lock
out 
OVLD START LEVEL 
(Motor Overload Start Level)   
This parameter defines maximum current 
at which motor can run continuously 
without triggering the motor overload.  
One of the two parameters that define the 
motor overload curve.  Set as a percent 
of Rated Motor Current. 
110 
100 – 150 
N Y 
OVLD TIME OUT 
(Motor Overload Time Out)   
This parameter defines the amount of 
time before a motor overload alarm 
occurs when the motor is running at the 
current level defined below: 
⎟⎟
⎜⎜
+
current
motor
rated
LEVEL
START
OVLD
%
40
:
 
This is the other parameter used to define 
the overload curve. For more information 
on the motor overload curve, see 
sec 
60.0 
5.0 – 120.0 
N Y 
 
OVLD TIME OUT
  
This is the other parameter used to define the 
overload curve. 
The user can adjust the motor overload 
parameters.  Three overload curves are shown 
in the examples below.  Curve #1 is the default 
motor overload curve. 
 
 OVLD 
START 
LEVEL 
OVLD 
TIME 
OUT 
curve #1 
110% 
60 sec 
curve #2 
110% 
40 sec 
curve #3 
120% 
70 sec 
 
Motor Overload Parameters 
 
When the motor usage exceeds the user 
defined motor overload curve, the drive will 
declare a motor overload alarm. 
 
 
 
 
 
 
 
 
 
Under the POWER DATA display sub-menu, 
the MOTOR OVERLOAD (D2) value displays 
the accumulated percent of motor overload trip 
level reached.  Once this value reaches 100% 
the motor overload will trip and a motor 
overload alarm is declared by the drive.  
 
 
The drive will only declare a motor overload 
and the user is responsible for taking 
appropriate action to protect equipment.  
The motor overload alarm can also be 
assigned to a logic output.  See configuration 
sub-menu items, C3.
 
 
 
 
 
 
 
 
 
 
 
The drive can also be configured so that a 
motor overload event declares a Fault, which 
will automatically cause the drive to stop.  If 
this is desirable, the following needs to be 
completed: 
RUN/FAULT 
SUB MENU 
DATA ENT 
MOTOR OVERLOAD 
D2          100% 
•  logic output configured to MTR 
OVERLOAD 
•  logic input configured to EXT FAULT 
•  wire the EXT FAULT logic input terminal to 
the to MTR OVERLOAD logic output 
terminal 
•  wire the logic input common terminal to the 
logic output common  
With the above set-up, the drive will then 
declare an External Fault on a motor overload.
 
 
 
 
RUN/FAULT 
ALARM! 
MTR OVERLOAD 
SUB MENU 
DATA ENT