Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
LS Overtemp 
(fault)
 
One or more of the IGBT 
modules on the line side 
power bridge has exceeded 
105
°C (221°F). 
Overtemperature Problems 
 
Manually verify 3-speed blower has correct 
operation 
 
Inspect and clean air intake filters 
 
Verify ambient temperature is less than 45
°C 
 
Inspect IGBT modules for proper mounting 
 
Verify drive is sized correctly 
 
Possible defective temperature sensor 
Excessive Current Draw 
 
Decrease Accel / Decel rates 
 
Mechanical brake not releasing properly 
Excessive Field Weakening 
 
Verify Weak Field Motor Parameters (A5) 
LS Over Temp 
(alarm)
 
One or more of the IGBT 
modules on the line side 
power bridge has exceeded 
95
°C (203°F).
 
Overtemperature Problems 
 
Manually verify 3-speed blower has correct 
operation 
 
Inspect and clean air intake filters 
 
Verify ambient temperature is less than 45
°C 
LS Overvolt 
 
The line side power converter 
has detected an over-voltage 
condition. 
Low Input Voltage 
 
Check INPUT L-L VOLTS (A5) and UV FAULT 
LEVEL (A4) 
 
Verify proper input voltage and increase, if 
necessary, the input AC voltage within the 
proper range 
 
Check for missing input phase 
 
Check power line disturbances due to starting 
of other equipment 
Line Converter Problem 
 
Verify the line converter did not shutdown 
while the motor controller was in process of 
regeneration 
Check Parameter Settings 
 
Bad tuning of either the line side regulators 
Contactor Problem 
 
Verify motor contactor did not open while 
motoring 
88