Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
LS BRDG GND 
 
The hardware has detected a 
ground fault on the line side 
power bridge. 
IGBT Breakdown 
 
Inspect and measure for physical voltage 
breakdown damage on IGBTs and DC bus  
LS Charge 
 
The DC bus did not charge up 
within the expected time.
 
DC Bus did not charge within expected time 
 
Verify that the setting for INPUT L-L VOLTS 
(A5) is correct  
 
Verify that the PCM contactor is activated 
during a pre-charge attempt 
 
Verify that pilot relay K1 on PCB A8 is 
functioning 
CAUTION: There may be a short circuit on the DC 
bus.  Inspect for physical damage.
 
LS CHK Setup 
 
This fault is logged when a 
new program is loaded to the 
line side processor, and the 
default data is loaded for the 
parameter values.
 
Inconsistent Parameter Settings 
 
Verify Parameters settings in menu A1, A2, 
A3, A4, and A6 are correct 
LS Conn Off 
 
The power interface board has 
detected a missing or loose 
connector on the line side. 
Missing Connector 
 
Verify connectors are connected 
 
Verify connectors are properly seated 
LS Cube Data 
 
The cube data for the line side 
processor is invalid. 
Invalid Cube ID 
 
Verify LS Cube ID is seated correctly and not 
damaged 
LS Cube ID 
 
The generation of this fault is 
indicative of a bad processor 
board. 
Invalid Cube ID 
 
Indicates a bad processor board 
LS Curr Reg 
 
Measured current does not 
match the command current. 
Problem with Motor Contactor 
 
Verify that motor contactor is closing 
 
Verify motor contactor is not opening 
unexpectedly 
Faulty current feedback signals 
 
Verify that reported drive current is zero when 
drive is not operating 
 
Verify connections to current transducers 
Loss of gate power supply 
 
Check gate power supply 
Incorrect DC Bus Voltage reading 
 
Measure the dc bus with a meter 
 
Compare that with the value on the digital 
operator, DC BUS VOLTAGE (D2) 
Inaccurate Motor Parameters 
 
Verify motor nameplate values (A6) are 
entered correctly 
External Relay Timing 
 
Check for improper external relay timing 
Check Wiring 
 
Missing jumper wire at Customer Interface 
Board PCB, TB2 
LS DCU Data 
 
The DCU parameters 
checksum is invalid on the line 
side. 
Parameters Corrupted 
 
Check & re-enter Line Side parameters and 
power cycle the drive 