Magnetek TM7310rev01 Benutzerhandbuch

Seite von 126
Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
LS Hit Current 
LMT (alarm) 
 
The line side is or was being 
limited by the motoring current 
limit or regenerative current 
limit setting.  This can limit 
current into the dc bus leading 
to an under-voltage condition, 
or limit current into the line 
leading to a bus over-voltage 
condition. 
Improper Line Side Menu Parameters (A5) 
 
Verify and correct all Line side (A5) parameter 
data 
Low Line Voltage 
 
Input line voltage is too low causing current to 
be too high for the operating power level 
 
Verify INPUT L-L VOLTAGE (A5) 
LS HW/SW 
 
Motor side software is 
installed in the line side control 
board. 
Improper software 
 
Replace Line Side A1 Board with correct 
software or reprogram Line Side A1 board with 
correct program 
LS IGBT 1,2,3 
 
A de-saturation condition has 
been detected on the specified 
line side IGBT module. 
Faulty IGBT or momentary short 
 
Recycle Power on Drive 
LS IP Comm 
 
A fault has occurred in the 
communications channel 
between the Line side and 
Motor side processors.  This 
was detected on the line side. 
Miscommunication problem 
 
Verify proper software installed in Line Side 
and Motor Side processors 
 
If re-occurs, replace PCB A2 
LS Overcurr 
 
The hardware has detected an 
over-current condition on the 
line side power converter. 
Overcurrent Problem 
 
Check for a possible short circuit in motor or 
external power wiring. 
Poor Regulator Tuning 
 
Check parameters 
 
Lower value in PLL FILTER Fc (A5) 
Noise Glitch 
 
Power Cycle drive 
 
If re-occurs, check wiring for EMC Compliance
LS Overload 
 
An overload condition has 
been detected on the line side 
power bridge. 
Excessive Field Weakening 
 
Verify Weak Field motor parameter (A5) 
Accurate Motor Parameters 
 
Verify motor nameplate values are entered 
correctly 
Excessive Current Draw 
 
Decrease accel/decel rate 
 
Mechanical brake not releasing properly 
Motor Problem 
 
Check for motor failure 
Drive Sizing 
 
Verify drive sizing with motor ampere 
requirements.  May need a larger capacity 
drive 
87