Commissioning (software) 
 
4.6 Using drive-related I/Os by SIMOTION 
 
D410 
100
 
Commissioning Manual, 08/2008 Edition 
4.6.6 
Using high-speed outputs for output cams on D410 
Using high-speed outputs for output cams / DOs with D410 
Output cams are defined as being the position-dependent output of switching signals. The 
TO output cams and TO output cam track technology objects control the output of output 
cams for SIMOTION. 
The integrated digital outputs of the SIMOTION D can be used as cam output or as high-
speed output with write access to the user program. In order to be able to use the high-
speed outputs, one of the 39x message frames must be created.  
 
 
Note 
If I/O data is transferred using bus message frames, the update of the I/O data is subject to 
the set bus cycle. This means an I/O using a 39x message frame can change its status just 
once in each bus cycle of the PROFIBUS Integrated. 
For SIMOTION D onboard outputs, the outputs are controlled using direct write accesses to 
the hardware (i.e. bypassing the message frame). This means: 
• 
Write accesses to digital outputs act with a particularly short delay time because the write 
access is independent of the bus cycle. 
• 
A more accurate output of the cam output is possible 
For fast write accesses from the user program, the resulting delay time has the following 
form: 
• 
User program delay time -> terminal register: max. 75 μs 
• 
Load-dependent output delay time of the hardware for D410:  
L -> H: max. 400 μs  
H -> L: max. 100 μs 
 
High-speed outputs of output cams 
If you use the output as high-speed output of a cam output, for the configuration of the TO 
output cams / TO output cam track, enter the logical hardware address and the bit number of 
the used output in the configuration screen form of the TO. 
For additional information, see the 
SIMOTION Motion Control Output Cams and Measuring 
Outputs
 Function Manual.  
High-speed digital outputs 
If you use the output as high-speed digital output, create an I/O variable in SIMOTION 
SCOUT. The same addresses should be used for the high-speed digital outputs as those 
normally used for the digital outputs.