Commissioning (software)
4.6 Using drive-related I/Os by SIMOTION
D410
92
Commissioning Manual, 08/2008 Edition
4.6.4
Configuring free message frames by means of BICO
Overview
For the "free message frame configuring using BICO", dedicated message frames for the
data transmission are assigned to the associated drive objects (e.g. terminal modules).
Message frame type: Free message frame configuring using BICO (only slaves)
To allow SIMOTION to access the SINAMICS drive signals, e.g. I/Os, they must be
To allow SIMOTION to access the SINAMICS drive signals, e.g. I/Os, they must be
interconnected to the SINAMICS using BICO to the message frame. The "free message
frame configuring using" is a preferred solution when I/Os are to be divided channel-granular
between SIMOTION and SINAMICS and a module view is preferred.
Table 4-4
Drive object: Maximum number of PSDs
Maximum number of PSDs for the configuring of the PROFIBUS
message frames
Drive object
Input data
(from the SIMOTION D
viewpoint)
Output data
(from the SIMOTION D
viewpoint)
TM15 DI/DO
5
5
TM31
5
5
TM41
19
16
Control Unit (CU)
15
5
Free message frame configuring using the TM31 as example
The example describes the interconnection of a signal to the TM31 connected to a
SIMOTION D410.
Steps in configuring user-specific message frames using BICO:
● Configure a user-specific message frame
● Interconnect the message frame for TM31
● Create I/O variables in SIMOTION SCOUT
Steps in configuring user-specific message frames using BICO:
● Configure a user-specific message frame
● Interconnect the message frame for TM31
● Create I/O variables in SIMOTION SCOUT
Prerequisite
You have already created a project and configured a drive.