Commissioning (software)
4.6 Using drive-related I/Os by SIMOTION
D410
Commissioning Manual, 08/2008 Edition
Commissioning Manual, 08/2008 Edition
93
Configuring user-specific message frames
1. Double-click the "Insert I/O component" entry in "SINAMICS_Integrated" in the Project
Navigator and then select terminal module "TM31" from the "Operating type" field of the
dialog box shown.
2. Enter a name for the module to be inserted and confirm your entry with OK.
3. Double-click the "Configuration" entry at "SINAMICS Integrated" in the Project Navigator
3. Double-click the "Configuration" entry at "SINAMICS Integrated" in the Project Navigator
to open the "PROFIBUS Message Frame" screen form.
"Free message frame configuration with BICO" (message frame 999) is set for the
"Free message frame configuration with BICO" (message frame 999) is set for the
inserted TM31. Insert the number of PSDs (Process Status Data) for I/O data. Observe
the maximum possible number of PSDs for the various drive objects (see previous table).
An TM31, for example, supports five PSDs in both the send and the receive direction.
4. Enter the value 5 in the "Length" column in the "Input data" or "Output data" fields.
Figure 4-22 Inserting a specific number of PSDs for the I/O data.
5. Click "Transfer to HW Config" in order to transfer the data to HW Config and to read the
address space of the I/O data.