Commissioning (software) 
 
4.6 Using drive-related I/Os by SIMOTION 
D410 
Commissioning Manual, 08/2008 Edition 
97
 
4.6.5 
Expanding a message frame 
The message frame extension extends existing standard message frames (e.g. axis 
message frames) with additional process status data (PSD). These additional PSDs are then 
interconnected using BICO (e.g. to an actual speed value or to the status of a digital input).  
A message frame extension is then the preferred variant when I/Os are to be distributed 
between SIMOTION and SINAMICS and, for example, an axis view is preferred (drive-
related I/O should be appended to each axis message frame). 
Proceed as follows: 
1.  Insert a drive using the Drive Wizard and select PROFIBUS (drive), e.g. "standard 
message frame 103", for process data exchange. 
2.  Double-click the "Configuration" entry below "SINAMICS Integrated" in the Project 
Navigator in order to open the "PROFIBUS message frame" tab. 
The tab contains the default length of I/O data for the drive you inserted. As the 
addresses of I/O data have not yet been transferred to HW Config the default entry "???" 
is set. 
3.  Select the row of the object of which you want to expand the message frame. 
 
Figure 4-26  PROFIBUS message frame 
 
4.  Click "Add line" and select the "Message frame expansion" option in the menu shown. 
A new line which contains the message frame expansion is inserted below the current 
line. 
5.  Enter the "length" for the number of PSDs by which the message frame is to be extended 
in the Input data and Output data columns.