Invenco Group Ltd G7UPC Benutzerhandbuch

Seite von 67
G7OPT Integrator Manual, DWI-00175 S1 R15
3.2.1 Installation with Removal-Tamper Sensors
1. Obtain access to where the unit will be integrated into its system, paying attention to authorisation
by accredited staff.
2. Obtain custody of the unit and any documentation, cables and other ancillary products.
Adhere to the requirements for custody change, unpacking, etc. in [G7INTSEC] as appropriate.
3. Mount the unit, and others which it will be connected to, in accordance with the integrator’s
instructions and those of Invenco.
See §5.1 G7SDC Installation Guide or §5.2 G7UPC Installation Guide for details. If instructions
conflict, Invenco’s must take precedence; failure to observe this may compromise the unit’s
security and/or void its standards certification.
4. Connect the unit to all others that it is being integrated with.
Tamper connections will vary according to whether the Invenco unit is integrated standalone or in
an Invenco housing. Both methods are described in the appended installation guides. Removal
tampers are likely to have been connected already in the course of mounting the unit; additional
connections for tampers should be unnecessary.
3.2.2 Removal-Tamper Clearing and Promotion to Normal Operation
1. The unit is now integrated into the system; it is in the removal-tampered state. Power it up and
verify that restricted-mode operation is possible.
In removal tampered state:
• the UPC will display a slow (once a second) red flashing LED
• the SDC will display a “removal tamper” error message
2. To clear the removal-tampered state and enable the unit for normal operation requires a
cryptographically authenticated challenge and response between it and an authorisation device.
This transaction is performed under dual control, the two parties being a field engineer and a
control-centre operator.
(a) The field engineer must first request a challenge token from the integrated unit. This is
achieved by:
i. Connect the terminal to the workstation running TMSlite.
ii. (First time only) Click Add, enter the terminal connection details, then click OK.
Fig. 3.3: Terminal connection details.
iii. Select the terminal from the left-hand list, then click Connect.
Chapter 3. Tampers
15