Utica Boilers UB90-200 Installationsanweisungen

Seite von 50
6
Locating The Boiler
1. 
Select level location, central to piping systems served 
and close to vent and air intake terminals as possible.
2. 
Manufacture recommended accessibility clearances, if 
more stringent (i.e. larger clearances) than required 
fire protection clearances, must be used for boiler 
installation. Accessibility clearances may be achieved 
with use of removable walls or partitions.
3. 
Combustible clearances shown in Table 4 indicate 
required clearances per CSA listing. Minimum 1” 
(25 mm) clearance must be maintained between 
combustible construction and each of the right, top 
and back surfaces of boiler. Minimum 8” (203 mm) 
clearance is required on left side, to allow room for inlet 
air pipe. 18” (457 mm) clearance must be maintained 
at front where passage is required for cleaning or 
servicing, inspection or replacement of any parts 
that normally require such attention. Allow 24” (610 
mm) at front and left side and 8” (203 mm) at top for 
servicing. No combustible clearances are required to 
venting or combustion air intake piping.
Table 4  - BOILER CLEARANCES
Unit
Combustible 
Clearance
Accessibility, Cleaning, 
and Servicing
Top
1” (25 mm)
8” (203 mm)
Left Side
8” (203 mm)
24” (610 mm)
Right Side
1” (25 mm)
-
Base
1” (25 mm)
-
Front
0” (0 mm)
24” (610 mm)
Back
1” (25 mm)
-
Intake/Vent 
Piping
0” (0 mm)
-
All distances measured from boiler cabinet.
4. 
Keep boiler area clean of debris and free of flammable 
and combustible materials, liquids and vapors.
5. 
Install equipment in location which facilitates operation 
of venting and combustion air intake piping systems as 
described in this manual.
6. 
Advise owner to keep venting and combustion air 
intake passages free of obstructions. Both venting 
and combustion air intake piping systems connected 
to outdoors must permit flow through piping systems 
without restrictions for boiler to operate. 
7. 
Boiler shall be installed such that automatic gas 
ignition system components are protected from water 
(dripping, spraying, rain, etc.) during operation and  
service (circulator replacement, condensate trap, 
control replacement, etc.).
8. 
Boiler must be located where ambient temperatures 
(minimum possible room temperatures where boiler 
is installed assuming boiler is not in operation and 
therefore contributes no heat to space) are always 
above freezing temperature. 
9. 
If boiler is not level condensate drain lines will not 
function properly. Adjustable feet are located on boiler 
to make up for minor surface irregularities or tilt.
10. 
Wood frame or blocks may be used to raise boiler 
to maintain drain pitch or to be above external 
condensate pump reservoir.
11. 
Provide means for condensate drainage.
3 - LOCATING THE BOILER
Removal Of Existing Boiler From Common Vent 
System
When an existing boiler is removed from a common 
venting system, the common venting system is likely to be 
too large for proper venting of the appliances remaining 
connected to it. At the time of removal of an existing boiler, 
the following steps shall be followed with each appliance 
remaining connected to the common venting system 
placed in operation, while the other appliances remaining 
connected to the common venting system are not in 
operation.
1. 
Seal any unused openings in the common venting 
system.
2. 
Visually inspect the venting system for proper size and 
horizontal pitch and determine there is no blockage 
or restriction, leakage, corrosion or other deficiencies 
which could cause an unsafe condition.
3. 
In so far as is practical, close all building doors and 
windows and all doors between the space in which the 
appliances remaining connected to the common venting 
system are located and other spaces of the building. 
Turn on clothes dryer and any appliance not connected 
to the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhaust, so 
they will operate at maximum speed. Do not operate a 
summer exhaust fan. Close fire dampers.
4. 
Place in operation appliance being inspected. Follow 
lighting instructions. Adjust thermostat so appliances 
operate continuously.
5. 
Test for spillage at draft hood relief opening after 5 
minutes of main burner operation. Use flame of match 
or candle, or smoke from cigarette, cigar or pipe.