INSTALLATION Page 
13 
 
 
MOUNTING THE CIRCUIT BREAKER CELL 
 
The circuit breaker cell is designed to mount to 
the floor or shelf of the installation compartment. 
The floor or shelf to which the cell is mounted 
should be flat and level within 
± 0.5 mm (± 0.02 
in.).  If there are any noticeable gaps between 
the cell base and the mounting surface, fill them 
in using flat washers as spacers. 
 
Fasten the cell using four (4) M8 hex head bolts 
(Fig. 11). The tightening torque should be 120-
150 kgf-cm (9-11 ft-lb). 
 
MAIN CIRCUIT CABLE CONNECTIONS 
 
Route cables that connect to the circuit breaker 
cell to avoid interference with sharp edges and 
moving parts.  Observe minimum bending radius 
for the type of cable used. 
 
Power cables should be braced and/or laced to 
withstand short-circuit forces wherever such 
cables are unsupported.  Power cables should 
be adequately sized to carry the maximum 
continuous current in accordance with NEC 
requirements and should have an adequate 
voltage rating.  Cables should be dressed and 
terminated as appropriate to the voltage class 
and cable manufacturer’s recommendations. 
When terminating shielded cables, use 
termination kits appropriate for the system 
voltage to taper the insulation and reduce 
electrical stress.  Follow the manufacturer’s 
installation instructions provided with the 
termination kit. 
 
Fasten the cables to the main circuit terminals 
(Fasten the cables to the main circuit terminals 
Fig. 12).  Use 35 mm Class 8.8 M10 or M12 
hex head bolts, 2 flat washers,  a lock washer 
and a nut.  While securely preventing the nut 
from rotating with a wrench, torque the bolt to 
250-315 kgf-cm (18-23 ft-lb) for M10 bolts or 
450-565 kgf-cm (32-41 ft-lb) for M12 bolts. 
 
 
 
 
 
 
 
 
 
 
 
Use two wrenches to torque 
the connection to prevent 
applying excessive force to 
the terminal that can 
damage the frame. 
 
Fig. 11  Fastening Cell to Compartment Floor 
or Shelf 
 
Fig. 12  Fastening Cables to Main Circuit 
Terminals 
 
 
 
 