INSTALLATION 
 
 
 
Do not install this 
equipment in areas where 
unusual service conditions 
exist. Using this equipment 
in other than usual service 
conditions can result in 
equipment failure.
 
 
Toshiba HV6FS-MLD circuit breakers are 
intended for use in usual service conditions as 
defined in IEEE C37.20.2. The temperature of 
the cooling air (ambient air temperature) 
surrounding the breaker should be between the 
limits of -5
°C (23°F) and +40°C (104°F). The 
altitude of the equipment installation should not 
exceed 3300 ft (1000 m). 
 
In particular, avoid the following installation 
conditions: 
 
- Excessive 
dust 
- Corrosive 
gases 
-  Extreme variations in temperature 
-  Very high or low humidity 
- Vibrations 
- Inclined 
locations 
 
If there is a chance that condensation can occur 
 
 
            Fig. 10  Typical Circuit Breaker Nameplate 
 
at the installation location, a space heater should 
be installed inside the circuit breaker enclosure. 
 
NOTE: 
 Temperature, altitude or other 
conditions outside of the usual limits 
may require derating or other special 
equipment. Contact your nearest 
Toshiba representative for additional 
information. 
 
RATING VERIFICATION
 
 
Prior to Installation, the maximum fault current 
capacity of the power system at the point of 
installation should be verified.  This value must 
not exceed the symmetrical interrupting 
capability of the circuit breaker.  Fig. 10 
illustrates a typical circuit breaker nameplate. 
 
Do not exceed the ratings 
specified on the circuit 
breaker nameplate or 
system accessories. 
Underrated equipment can 
fail during operation 
causing fire, explosion, 
severe injury, death, and 
property damage.
 
 
 
 
 
    WARNING 
   
DANGER
HOUSTON, TEXAS U.S.A.
RATED VOLTAGE
FREQUENCY
IMPULSE LEVEL
DIELECTRIC
SER. No.
PARTS & WIRING, SEE INSTRUCTIONS
CONTINUOUS AMPS
WEIGHT
SHORT CKT. AMPS
INTERRUPTING TIME
VACUUM CIRCUIT BREAKER
MFG. STANDARD
SHUNT TRIP VOLTS
TOSHIBA INTERNATIONAL CORPORATION
CLOSE VOLTS
  50/60 Hz
  22 kV AC RMS
 60 kV, CREST
630A, RMS
kg
MFG. DATE
lbs
HV6FS-
   7.2/4.8 kV, RMS
TYPE
    JIS C 4603-1990
   JEC-2300-1985
VDC
VDC
14/16 kA, RMS
3 CYCLES
38
84
125
125
GF07Z304
MLD-VVU
03700235
7/03
TOSHIBA
UV TRIP VOLTS
VAC
120
 