greater than the value of Parameter 4 (t1 top). there 
is no concern that temperature boost would supply 
water too hot for low-temperature systems, such as 
slab-type radiant heating. On hybrid systems, with 
finned tube radiation and radiant slab, provide additional 
low temperature protection for the radiant portion of the 
system, because Parameter 4 (t1 top) is likely to be 
set higher than on a radiant-only system.
IMPORTANT: Many slab-type radiant systems 
won’t  require  boost.  This  function  can  be  dis-
abled with a parameter 11 setting of “0.”
Boost operation
in outdoor reset operation (outdoor sensor connected), 
1. 
the boiler control automatically increases the target out-
let water temperature if a call for heat exceeds a time 
equal to Parameter 11 (factory default of 30 minutes).
at each interval of Parameter 11 of a continuous call for 
2. 
heat, the control module increases the target tempera-
ture by 18° F. See 
Figure #3.
the control module will continue increasing target 
3. 
temperature until it reaches the value set in Parameter 
4 (t1 top).
When the call for heat ends while target temperature is 
4. 
“boosted,” the target temperature drops about 2° F for 
III - PARAMETER ExPLANATIONS
 PARAMETER 11 (automatic supply temperature booster operation)
Temperature Boost Operation (typical): in this example, the boiler is operating in outdoor reset mode with a calculated setpoint tem-
perature of 130°F. the call for heat has lasted more than 10 minutes (value of Parameter 11) and supply temperature boost has occured.
Figure #3
each minute the thermostat is open.
Range: 1-30 minutes.
5. 
Factory default: 30 minutes.
6. 
deactivate automatic temperature boost by setting to 
7. 
“0.”
MAxIMUM FAN SPEED
Fan  speed  must  be  set  within  the  limits  sup-
plied  by  the  factory  (See  the  “Default  Param-
eters table” 
in Section II). Setting limits above 
or below these factory defaults would increase 
or  decrease  boiler  firing  rate  beyond  the  ac-
ceptable limit, resulting in potential for severe 
personal  injury,  death,  or  substantial  property 
damage.
WARNING
!
  
Parameters 13 and 15 can be set to limit the maximum 
• 
boiler firing rate. Boiler firing rate is proportional to the 
fan speed, so reducing the maximum fan speed reduc-
es maximum input.
Reducing maximum fan speed will be helpful for sys-
• 
tems on which the boiler is oversized for either space 
heating or dHW, or both.
maximum fan speed can be set separately for space 
•