Utica Boilers UB95M-200 Verweisanleitung

Seite von 20
9
BOILER FIRING RATE VS. RPM
% Rate
BTUH
RPM
Boiler Display
40
80,000
2250
22
50
100,000
3250
32
60
120,000
3800
38
70
140,000
4400
44
80
160,000
4750
47
90
180,000
5250
52
100
200,000
6000
60
NOTE: Results may vary depending on altitude of in-
stallation, gas calorific value, and vent length.
heating and dHW using Parameters 13 and 15.
Parameter 13 (space heating max. fan speed):
acceptable Range for natural gas and LP: 2250 to 
• 
6000 rpm (22 to 60 on boiler display).
nOte: Boiler display shows fan speed in hundreds of rpm. a 
value of 48 would mean a speed of 100 x 48, or 4800 rpm.
Factory defaults: See the “default Parameters table” in 
• 
Section ii of this manual.
if the boiler is oversized for space heating, you can 
• 
reduce the maximum fan speed during space heating 
operation (Parameter 13) to limit the maximum boiler 
input.
Parameter 15: DHW max fan speed
acceptable Range for natural gas and LP: 2250 to 
• 
6000 rpm (22 to 60 on boiler display).
nOte: Boiler display shows fan speed in hundreds of rpm. a 
value of 48 would mean a speed of 100 x 48, or 4800 rpm.
Factory defaults: See the “default Parameters table” in 
• 
Section ii of this manual.
if the boiler is oversized for domestic water heating, you 
• 
can reduce the maximum fan speed during dHW opera-
tion (Parameter 15) to limit the maximum boiler input.
MINIMUM FAN SPEED (PARAMETER 17)
The fan speed must not be set below the value 
as  supplied  from  the  factory  (see  the  “Default 
Parameters  table”
  in  Section  II).  This  would 
reduce boiler firing rate below the acceptable 
limit, resulting in potential for severe personal 
injury, death, or substantial property damage.
WARNING
!
  
PARAMETER 17
 sets the minimum fan speed. Boiler firing 
rate is proportional to fan speed, so increasing the minimum 
fan speed increases the minimum firing rate (low fire).
Parameter  17  sets  the  minimum  fan  speed  for  both  dHW 
and  space  heating  modes.  set  parameter  17  to  3,200  for 
altitudes above 2,000 ft.
acceptable Range for natural gas and LP: 2250 rpm 
• 
(22 on boiler display).
nOte: Boiler display shows fan speed in hundreds of rpm. a 
value of 48 would mean a speed of 100 x 48, or 4800 rpm.
Factory defaults: See the “default Parameters table” in 
• 
Section ii of this manual.
III - PARAMETER ExPLANATIONS
IGNITION FAN SPEED (PARAMETER 19)
The fan speed must not be set BELOW the value 
as  supplied  from  the  factory  (see  the  “Default 
Parameters  Table”  in  Section  II).  This  would 
reduce boiler firing rate below the acceptable 
limit, resulting in potential for severe personal 
injury, death, or substantial property damage.
WARNING
!
  
Parameter 19 sets the fan speed during ignition. Boiler 
• 
firing rate is proportional to fan speed, so increasing the 
minimum fan speed increases the minimum firing rate 
(low fire).
IMPORTANT: 
Parameter 19 should only be changed where 
required for high altitude applications.
acceptable Range for natural gas and LP: 3000 to 
• 
3600 rpm (30 to 36 on boiler display).
nOte: Boiler display shows fan speed in hundreds of rpm. a 
value of 48 would mean a speed of 100 x 48, or 4800 rpm.
Factory defaults: See the “default Parameters table” in 
• 
Section ii of this manual.
DIFFERENTIAL (HySTERESIS) SETTINGS
Do not change the differentials (hysteresis) for 
domestic  hot  water  operation  (Parameters  24, 
25, 26, and 27). Always use only the factory de-
fault settings for these parameters.
WARNING
!