Communication Manager Maintenance-Object Repair Procedures
1240 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
EXT-DEV (External device alarm)
G650
A TN2312BP IPSI, in a G650 with a carrier address set to A, has two alarm ports that connect to 
external devices. An example of an external device is an uninterruptible power supply (UPS). 
Refer to 
further information.
Conditions can occur on the external device that close the contacts on the alarm leads. This 
notifies the switch to originate an EXT-DEV alarm. One set of leads generates a major alarm, 
the other set generates a minor alarm.
In this case, the designation of major or minor refers to the port, not to the severity of the alarm 
associated with the connection. For example, the major port can be administered as a major, 
minor, or warning alarm, and the minor port can be administered as a major, minor, or warning 
alarm. Analog line ports can also be administered as external device alarms in the same 
manner.
Error log entries and test-to-clear values
-
MO name in
alarm Log
Alarm 
level
Initial SAT command to run
Full name of MO
EXT-DEV
MIN
test environment location
External Device Alarm
EXT-DEV
MAJ
test environment location
External Device Alarm
EXT-DEV
MIN
test eda-external-device-alm location
External Device Alarm
EXT-DEV
MAJ
test eda-external-device-alm location
External Device Alarm
Table 421: Test to clear with external device alarm administration enabled
Error 
Type
Aux 
data
Associated test
Alarm 
level
On/Off 
board
Test-to-clear value
1
Alarm query test 
(#120)
MAJ
MIN
OFF
test eda-external-device-alm 
location
Table 422: Test-to-clear without external device alarm administration enabled
Error 
type
Aux 
data
Associated test
Alarm 
level
On/Off 
board
Test-to-clear value
1
Alarm query test (#120) MAJ 
MIN
OFF
test environment location