Communication Manager Maintenance-Object Repair Procedures
1246 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
EXT-DEV ADMIN? Y (External Device Alarm)
S8700 | 8710
 / 
S8500
Note:
Note:
Use this MO when the External Device Alarm Admin field on the change 
system-parameters customer-options
 screen is y. You must have INADS 
or INIT login permissions to administer EXT-DEV Alarm.
S8700 | 8710
 / 
S8500
Each PN’s Maintenance circuit pack has two alarm ports that connect to such external devices 
as uninterruptible power supplies (UPSs) or adjuncts (e.g., AUDIX).
Certain conditions on the external device close the contacts on the alarm leads to notify the 
switch that in turn originates an EXT-DEV alarm. One set of leads generates a major alarm; the 
other set generates a minor alarm.
The special locations UUmajor and UUminor are used to designate the major or minor 
Maintenance board’s alarm connection for cabinet UU. The major/minor designation specifies 
the port, not the alarm level associated with the connection; for example, the “major” port can be 
administered as a major, minor, or warning alarm, and the “minor” port can be administered as a 
major, minor, or warning alarm. In addition Analog line ports can also be administered as 
external device alarms.
Note:
Note:
An un-administered Maintenance board’s external device alarm port, that is 
sensing a contact closure will have an entry in the Error Log and in the Alarm 
Log. The alarm receiver will not receive warning alarms.
MO Name in 
Alarm Log
Alarm 
Level
Initial SAT Command to Run 
1
1. UU is a cabinet number determined in the 
Port
 field of the Alarm or Error Log.
Full Name of MO
EXT-DEV
MAJ
test eda-external-device-alrm UU External Device Alarm
EXT-DEV
MIN
test eda-external-device-alrm UU External Device Alarm
EXT-DEV
WRN
test eda-external-device-alrm UU External Device Alarm