Communication Manager Maintenance-Object Repair Procedures
1532 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Control Channel Loop-Around Test (#52)
This test queries the circuit pack for its circuit pack code and vintage and verifies its records.
Table 553: Test #52 Control Channel Loop-Around Test 
Error
Code
Test
Result
Description / Recommendation
None 
2100
ABRT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
The circuit pack failed to return the circuit pack code or vintage.
1. Retry the command up to 5 times.
2. If the problem continues, and if the circuit pack is one of the Port 
circuit packs, replace the circuit pack.
3. Otherwise, if the circuit pack is part of the SPE, use the procedure 
described in 
 in Maintenance 
Procedures (03-300192).
PASS
Communication with this circuit pack is successful.
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This could 
be due to incorrect translations, no board is inserted, an incorrect board is 
inserted, or an insane board is inserted.
1. Ensure that the board translations are correct. Execute add ds1 
location to administer the MAPD interface if it is not already 
administered.
2. If the board was already administered correctly, check the error log to 
determine whether the board is hyperactive. If so, the board was shut 
down. Reseating the board re-initializes it.
3. If the board was found to be inserted correctly, enter busyout 
board.
4. Enter the reset board command.
5. Enter the release board command.
6. Enter the test board long command.
This should re-establish the linkage between the internal ID and the port.