Communication Manager Maintenance-Object Repair Procedures
1898 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
SCOTCH Synchronous Loop-Around Test (#1275)
This test is destructive.
This test verifies the circuit in the data path of a PPP call. This test fails if the data transmitted on 
the port does not match the data received in the loop-around mode. Failure of this test indicates 
a port hardware fault on the circuit pack.
This test aborts if calls are using the port, or if the PPP link associated with the port is 
connected. To avoid this, first enter busyout data-module extension, or busyout port 
location
, or busyout link link#, which will cause every call and link using the port to be 
torn down.
2000
ABRT
Did not receive circuit pack test response within the allowable time period.
1. If this problem persists, reset the circuit pack (busyout board 
locationreset board location, and release board 
location
).
2. If the problem persists, replace the circuit pack.
2012
ABRT
Internal system error.
1. Retry the command at 1-minute intervals up to 3 times.
2100
ABRT
Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
Received tones do not match transmitted tones.
1. Retry command at 1-minute intervals up to 3 times.
2. If the problem persists, see 
3. If the problem persists, reset the board (busyout board 
locationreset board location, and release board 
location
). Repeat the test.
4. If the problem persists, replace the circuit pack.
PASS
Port connections across the TDM bus function properly.
Table 692: Test #1285 TDM Loop-Around Test (continued)
Error
Code
Test
Result
Description / Recommendation
 2 of 2