Communication Manager Maintenance-Object Repair Procedures
2132 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Error Log Entries and Test to Clear Values
Notes:
a. Error Type 0: Run the short test sequence first. If every test passes, run the long test 
sequence. Refer to each test’s description, and follow its procedures.
b. Error Type 1: this Error Type corresponds to FAIL code 1 of the Stratum-3 Clock Alarm 
Query test (#649): either reference A failed or the CI card A failed.
c. Error Type 18: Synchronization Maintenance was disabled using disable 
synchronization-switch
1. Execute enable synchronization-switch to enable Synchronization Maintenance 
reference switching and to resolve this alarm.
d. Error Type 257: this Error Type corresponds to FAIL code 2 of the Stratum-3 Clock Alarm 
Query test (#649): one power supply failed.
e. Error Type 513: this Error Type corresponds to FAIL code 4 of the Stratum-3 Clock Alarm 
Query test (#649): one clock unit failed.
Table 764: Stratum-3 Clock Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
0 (
)
0
Any
Any
Any
test synchronization r 4
1 (
)
Any
Stratum-3 Clock Alarm 
Query (#649
MIN
OFF
test synchronization r 4
18 (
)
0
disable sync
WRN
OFF
enable sync
257 (
)
Any
Stratum-3 Clock Alarm 
Query (#649)
MIN
OFF
test synchronization r 4
513 (
)
Any
Stratum-3 Clock Alarm 
Query (#649
MIN
ON
test synchronization r 4
769 (
Any
Stratum-3 Clock Alarm 
Query (#649)
MIN
ON
test synchronization r 4
1025 (
)
Any
Stratum-3 Clock Alarm 
Query (#649)
MIN 
ON
test synchronization r 4
1281 (
)
Any
Stratum-3 Clock Alarm 
Query (#649)
MIN 
ON
test synchronization r 4
1537 (
none
MIN 
ON
1793 (
none
MIN 
ON