Communication Manager Maintenance-Object Repair Procedures
2280 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
1003
ABRT
The system could not allocate a tone receiver for the test. The 
system may be oversized for the number of tone detectors present 
or some of the tone detectors may be out of service. Enter list 
measurements tone-receiver
 to display basic information 
about the system's tone receivers.
1. Resolve any TTR-LEV errors.
2. Resolve any TONE-PT errors.
3. If neither condition exists, retry the test at 1-minute intervals up 
to 5 times.
1004
ABRT
The port was seized by a user for a valid call.
1. Use display port location to determine the trunk group/
member number of the port. Use status trunk to determine 
the service state of the port. If the service state indicates that 
the port is in use, then the port is unavailable for certain tests. 
Wait until the port is idle before retesting.
2. If the port status is idle, retry the command at 1-minute intervals 
up to 5 times.
1018
ABRT
Test disabled by administration. This only applies to analog 
stations.
1. To enable test, set the Test field on the Station Administration 
form (change station extension) for the particular analog 
station being tested to y.
1020
ABRT
The test did not run due to a previously existing error on the specific 
port or because of a more general circuit pack error.
1. Examine the Error Log for existing errors against this port or 
circuit pack, and attempt to diagnose the previously existing 
error.
S8500
 / 
G700
:
1412
ABRT
This test does not execute on a G700 Media Gateway.
2000
ABRT
Response to the test request was not received within the allowable 
time period.
1. Retry the command at 1-minute intervals up to 5 times.
Table 816: Test #7 Conference Circuit Test  (continued)
Error
Code
Test
Result
Description / Recommendation
 2 of 5