Avaya 03-300430 User Manual

Page of 2574
TONE-PT (Tone Generator)
Issue 1 June 2005
2359
 
Notes:
Except in EPNs containing more than one IPSI or Tone-Clock circuit pack, replacing an IPSI or 
Tone-Clock circuit pack is a service disrupting procedure. The test should be run several times 
with more than one failure before the replacement policy specified in the following notes is 
executed. Use the procedure described in 
2000
ABRT
Response to the test request was not received within the allowable 
time period. System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2100
ABRT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1 (
FAIL
DTMF generation failed for the active tone generator.
105 (
)
FAIL
Generation of 440-Hz failed.
109 (
)
FAIL
Generation of 2225-Hz failed.
)
FAIL
Generation of 404-Hz level invalid.
111 (
FAIL
Generation of 1004-Hz low level invalid.
)
FAIL
Generation of 1004-Hz high level invalid.
)
FAIL
Generation of 2804-Hz level invalid.
FAIL
Generation of digital count sequence invalid.
120 (
)
FAIL
Generation of quiet tone failed.
1044 (
)
FAIL
DTMF generation failed to generate Digit 1 for the standby tone 
generator.
1045 (
)
FAIL
DTMF generation failed to generate Digit 5 for the standby tone 
generator.
1046 (
)
FAIL
DTMF generation failed to generate Digit 9 for the standby tone 
generator.
1047 (
)
FAIL
DTMF generation failed to generate Digit D for the standby tone 
generator.
PASS
The tone generation facility is able to generate and transmit all the 
tones.