Communication Manager Maintenance-Object Repair Procedures
754 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Notes
a. Error Type 1: the inlet temperature is over the threshold—120
Fahrenheit (49
Celsius). 
Run test board and check results of Test #1537.
b. Error Type 257: the exhaust temperature is over the threshold—120
Fahrenheit (49
Celsius). Run test board and check results of Test #1537.
c. Error Type 513: the hot spot temperature is over the threshold. Run test board and 
check results of Test #1537.
d. Error Type 769: the fan alarm is active. Run test board and check results of Test #1537.
System technician-demanded tests:
Descriptions and error codes
Investigate tests in the order presented
Power supply temperature test (#1537)
The power supply temperature test provides the status of the following temperatures:
Inlet to the power supply (120F/49C)
Carrier exhaust (120F/49C)
Power supply hot spot status
513 (
)
Power supply 
temperature test (#1537)
MIN/ 
MAJ 
1
ON
test enviroment location
test board location
769 (
)
Power supply fan test 
(#1538)
MIN
ON
test enviroment location
test board location
1. This is a minor alarm if there is a redundant power supply, and a major alarm if there is only one power 
supply.
Table 259: CAB-TEMP Error Log Entries 
Error 
Type
Aux 
data
Associated test
Alarm 
level 
On/Off 
board
Test-to-clear value
Order of investigation
Short test 
sequence
Long test 
sequence
D/ND
Power supply temperature test (#1537)
X
X
Nondestructive
Power supply fan test (#1538)
X
X
Nondestructive