CAB-TEMP (Cabinet Temperature)
Issue 1 June 2005
757
 
Power supply fan test (#1538)
The power supply fan test verifies that the fan alarm lead from the fan assembly is not active.
Table 261: Test #1538 power supply fan 
Error 
code
Test 
result
Description and recommendation
1000
ABRT
This is an internal software error. 
1035
ABRT
The port network is not available.
2028
ABRT
There is a problem communicating with the environmental maintenance 
firmware.
2100
ABRT
The system could not allocate resources.
1. Repeat the command at one-minute intervals 1 to 3 times.
2319
ABRT
The EPN is out of range.
2500
ABRT
An internal operation failed. Retry the command.
FAIL
The fan alarm lead from the fan assembly is active. 
1. Verify proper operation of the fan assembly.
2. Replace the fan assembly.  See 
 in 
PASS
The fan alarm lead from the fan assembly is not active. 
NO 
BOARD
The power supply is administered but not detected.
1. Verify that the power supply is plugged in.
2. Replace the power supply.