ICP-CC488 | Installation Guide | 14.0  
Zone Information 
EN | 63 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
5 – Latching Arm in STAY Mode 1 
The system is armed in STAY Mode 1 when using 
the latching keyswitch input. Arming the system in 
AWAY Mode or disarming the system is not 
permitted from the Keyswitch Zone. 
6 – Latching Disarm from STAY Mode 1 or STAY 
Mode 2 
The system is disarmed from STAY Mode 1 or 
STAY Mode 2 when using the latching keyswitch 
input. Arming the system in STAY Mode 1 or STAY 
Mode 2, or arming and disarming the system in 
AWAY Mode is permitted from the Keyswitch Zone. 
8 – Momentary Arm and Disarm in AWAY Mode 
The system is armed or disarmed from AWAY Mode 
when using the momentary keyswitch input. 
9 – Momentary Arm in AWAY Mode 
The system is armed in AWAY Mode when using 
the momentary keyswitch input. Disarming the 
system is not permitted from the Keyswitch Zone. 
10 – Momentary Disarm from AWAY Mode, STAY 
Mode 1, or STAY Mode 2 
The system is disarmed from either AWAY Mode, 
STAY Mode 1, or STAY Mode 2 when using the 
momentary keyswitch input. Arming the system is 
not permitted from the Keyswitch Zone. 
12 – Momentary Arm and Disarm in STAY Mode 1 
The system is armed or disarmed in STAY Mode 1 
when using the momentary keyswitch input. Arming 
and disarming the system in AWAY Mode is not 
permitted from the Keyswitch Zone. 
13 – Momentary Arm in STAY Mode 1 
The system is armed in STAY Mode 1 when using 
the momentary keyswitch input. Arming the system 
in AWAY Mode or disarming the system is not 
permitted from the Keyswitch Zone. 
14 – Momentary Disarm from STAY Mode 1 or 
STAY Mode 2 
The system is disarmed from STAY Mode 1 or 
STAY Mode 2 when using the momentary keyswitch 
input. Arming the system in STAY Mode 1 or STAY 
Mode 2, or arming and disarming the system from 
AWAY Mode is not permitted from the Keyswitch 
Zone. 
Figure 14:  Wiring Diagram for Keyswitch Zone 
 
 
1 – EOL 
2 – Keyswitch (Momentary/Toggle) 
 
Figure 15:  Wiring Diagram for Keyswitch Zone 
Using Split EOL with Tamper 
 
 
1 – EOL 
2 – Keyswitch (Momentary/Toggle)
 
14.3.7 
Zone Options 2 
This location has four programming options. You can 
select any combination of the options by 
programming a single value. Calculate this value by 
adding the option bit numbers together. Refer to 
Section 7.3 Programming Option Bits on page 36 for 
more information. 
Table 52:  Zone Options 2 
 
Option 
Description 
Isolate in STAY Mode 1 
2 Zone 
Isolation 
Allowed 
4 Forced 
Arming 
Allowed 
Zone Restore Report 
1 – Isolate in STAY Mode 1 
If this option is selected, the zone can be 
automatically isolated when the system is armed in 
STAY Mode 1.   
If this option is not selected and the system is armed 
in STAY Mode 1, the zone activates an alarm when 
activated as it normally would in AWAY Mode.  
You can specify a global entry time for all zones, 
except for 24-Hour Zones, when the system is armed 
in STAY Mode 1. You program this time in 
Locations 472 and 473 (refer to Section 17.5 Entry 
Guard Timer for STAY
 Mode on page 78). The Entry 
Guard Timer overrides the delay time programmed 
for a Delay Zone. If you program the Entry Guard 
Timer as 0, each zone acts according to its 
programmed zone type. 
Refer to Section 3.3 Arming the System in STAY Mode 1 
on page 14 for more information. 
2 – Zone Isolation Allowed 
If this option is selected, the operator can isolate the 
zone before arming the system. If this option is not 
selected, the zone cannot be manually isolated. 
When a zone is manually isolated, a Zone Bypass 
Report (Contact ID Event Code 570) is sent. Refer to 
Section 3.11 Isolating Zones on page 17 for more 
information.