(c) Economy mode 
The UPS switches to Economy mode when the input power voltage is within a certain 
range and the output power factor is above a certain value. In Economy mode, the UPS 
receives power from the utility power source and supplies it to the load. At the same 
time, the inverter is connected to the load and ready to activate. The batteries are kept 
continually charged and ready in case a problem (outage or voltage drop) occurs in the 
utility supply. 
 
 
 
 
 
 
 
 
 
 
 
Power supply route in Economy mode                                    Indications by LEDs 
 
(2)  On Failure of Utility Power   
When a fault or an outage occurs in the utility power source, the rectifier and charger 
cease operating while inverter operation continues, now using the batteries as a DC source 
to produce AC voltage, to ensure stable power supply to the load without even a 
momentary power dropout. At the same time, the buzzer sounds the battery operation 
alarm, and the green INPUT indicator starts blinking. 
 
 
 
 
 
 
 
 
 
 
Power supply route on failure of utility power                          Indications by LEDs 
 
(3)  Upon Recovery of Utility Power 
When normal utility power is restored, rectifier and charger operations resume 
automatically, returning to the normal operating state described in §15.1 (1). 
 
(4)  When Battery Voltage Declines 
When low voltage or an outage in the utility power source continues, causing the battery 
voltage to decline to about 45V (1.85V/cell), the red BATT.LOW indicator in the above 
figure lights to indicate low battery voltage.   
 
Note: When item  ⑫  “Low battery voltage signal timing” in §10.1 “Setup Menu Item List” 
is set to “2 minutes” or “3 minutes”, the alarm is issued at the point when the 
remaining battery time drops to the specified level. 
 
(5)  Extended Power Outage 
If a power outage persists and the battery voltage reaches the final discharge level, a 
protective circuit shuts off the inverter to prevent over-discharging of the batteries. When 
normal utility power recovers after the inverter has been stopped automatically, operation 
is automatically resumed, returning to the normal operating state described in §15.1 (1). 
 
Note: When  item  ⑦ “Restart time” in §10.1 “Setup Menu Item List” is set to “OFF”, 
inverter output remains stopped. When it is set to “30%”, “50%”, or “80%”, the UPS 
restarts operation once the batteries are charged to the specified level and then 
returns to the normal operating state described in §15.1 (1). 
 
Utility 
power 
Output
 
Converter 
Rectifier 
Inverter
 
Charger
 
Batteries
 
 
Utility 
power 
 
 
 
Output
 
Converter 
Inverter 
 
Charger
 
Batteries
 
Rectifier