Schneider Electric 230 VAC User Manual

Page of 20
Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
12
Troubleshooting
Problem and Possible Cause
Solution
The UPS will not turn on or there is no output
The unit has not been turned on.
Press the 
ON
 button once to turn on the UPS.
The UPS is not connected to utility 
power.
Ensure that the power cable is securely connected to the unit and to the utility 
power supply.
The input circuit breaker has tripped.
Reduce the load to the UPS, disconnect nonessential equipment and reset the 
circuit breaker.
The unit shows very low or no input 
utility voltage.
Check the AC power supply to the UPS by plugging in a table lamp. If the 
light is very dim, check the utility voltage.
The battery connector plug is not securely 
connected.
Ensure that all battery connections are secure.
There is an internal UPS fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced 
immediately.
The UPS is operating on battery, while connected to input utility power
The input circuit breaker has tripped.
Reduce the load to the UPS, disconnect nonessential equipment and reset the 
circuit breaker.
There is very high, very low, or distorted 
input line voltage. 
Move the UPS to a different outlet on a different circuit. Test the input voltage 
with the utility voltage display. If acceptable to the connected equipment, 
reduce the UPS sensitivity.
UPS is emitting an audible beeping sound
The UPS is in normal operation.
None. The UPS is protecting the connected equipment.
UPS does not provide expected backup time
The UPS battery is weak due to a recent 
outage or is near the end of its service 
life.
Charge the battery. Batteries require recharging after extended outages and 
wear out faster when put into service often or when operated at elevated 
temperatures. If the battery is near the end of its service life, consider 
replacing the battery even if the replace battery indicator is not yet 
illuminated.
The UPS is overloaded.
Check the UPS load display. Unplug unnecessary equipment, such as printers.
Display interface indicators flash sequentially
The UPS has been shut down remotely 
through software or an optional accessory 
card.
None. The UPS will restart automatically when utility power returns.
The Fault indicator is lit and the UPS displays a fault message and emits a constant beeping sound
Internal UPS fault.
Do not attempt to use the UPS. Turn the UPS off and have it serviced 
immediately.
All indicators are illuminated and the UPS is plugged into a wall outlet
The UPS has shut down and the battery 
has discharged from an extended outage.
None. The UPS will return to normal operation when the power is restored 
and the battery has a sufficient charge.