Schneider Electric 230 VAC User Manual

Page of 20
11
Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
Emergency Power Off
EPO Overview
The Emergency Power Off (EPO) option is a safety feature that will immediately disconnect all 
connected equipment from utility power. The UPS will immediately shut down and will not switch to 
battery power.
The UPS must be manually restarted to reapply power to connected equipment. Press 
O
N
/O
FF
 
on the front 
panel of the unit.
Normally open contacts
1. If the EPO switch or relay contacts are normally open, insert the wires 
from the switch or contacts at pins 1 and 2 of the EPO terminal block. 
Use 16-28 AWG wire. 
2. Secure the wires by tightening the screws. 
If the contacts are closed, the UPS will turn OFF and power will be removed from the load.
Normally closed contacts
1. If the EPO switch or relay contacts are normally closed, insert the wires 
from the switch or contacts at pins 2 and 3 of the EPO terminal block. 
Use 16-28 AWG wire. 
2. Insert a wire jumper between pins 1 and 2. Secure the wires by 
tightening the three screws at positions 1, 2, and 3.
If the contacts are opened, the UPS will turn OFF and power will be removed from the load. 
Note: The power for operating the EPO circuit is sourced from pin 1. This is an isolated 24 V which can 
source only a few milliamperes.
If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for "dry" 
circuit applications, the rating should be for low voltage and low current applications. This normally 
implies the contacts are gold-plated.    
Adhere to all national and local electrical codes when wiring the EPO. Wiring must be performed 
by a qualified electrician.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to 
other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. 
SELV circuits are controlled by a switch or relay properly isolated from utility power. To avoid damage 
to the UPS, do not connect the EPO interface to any circuit other than a SELV circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
•  CL2: Class 2 cable for general use.
•  CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
•  CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
•  CLEX: Limited use cable for use in dwellings and for use in raceways.
•  Installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).
•  Installation in countries other than Canada and the USA: Use standard low-voltage cable in 
accordance with national and local regulations.
gen
08
87
a
gen
08
88a