Schneider Electric 230 VAC User Manual

Page of 20
13
Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
The replace battery indicator is illuminated
The battery has a weak charge.
Allow the battery to recharge for at least four hours. Then, perform a self-test. 
If the problem persists after recharging, replace the battery.
The replacement battery is not properly 
connected.
Ensure that the battery connector is securely connected.
The display interface has a Site Wiring Fault message
Wiring faults detected include missing 
ground, hot-neutral, polarity reversal, 
and overloaded neutral circuit.
If the UPS indicates a site wiring fault, have a qualified electrician inspect the 
building wiring. (Applicable for 120 V units only.)
Problem and Possible Cause
Solution