Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
Wiring Recommendations
111
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
Wiring Diagram for ATV58 TRX Type F Controllers (Single Phase)
M
3
φ
Brake
Resistor
(5)
PA
PB
ATV58E
Other Models
T1
T2
T3
U
V
W
+
-
ATV58E
U09M2FZU
and U18M2FZU
Brake
Module
Brake
Resistor
PA
PB
+
-
(5)
(2)
L1
L2
(4)
(6)
R1A
R1C
R1B
K13
K14
AO
1
COM
AI1
+10
COM
AI2
LI3
LI1
LI2
+24
LI4
Fault
Manual
Speed
Potentiometer
(3)
L1
L2
F1
F2
(1)
Line
Reactor
Start-Stop Push Buttons 
with Seal-in Relay
ST
OP
ST
AR
T
Notes
1. Line inductor, if required.
2. Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with 
the controller de-energized or faulted.
3. User-installed wiring for using LI2, LI3, and LI4 with internal +24 V power supply. When using a 
+24 V external supply, connect the 0 V to the COM terminal. Do not use the +24 terminal on the 
control board but connect logic inputs to external +24 V.
4. K13 and K14 are open terminals available for customer use.
5. Use dynamic braking module VW3A58701 with drive controllers ATV58EU09M2FZU and 
U18M2FZU if dynamic braking is required. See page 34 for available braking resistor kits.
6. Manual speed potentiometer and start-stop push buttons are factory-installed in the enclosure 
cover. There is enough space in the cover to install one more 16-mm operator.
1
 P
h
as
e T
y
pe
 F