Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
Wiring Recommendations
©
 2000–2003 Schneider Electric All Rights Reserved
112
09/2003
Wiring Diagram for ATV58 TRX Type F Controllers (Three Phase)
M
3
φ
Brake
Resistor
(5)
PA
PB
T1
T2
T3
U
V
W
(2)
L1
L3
(4)
R1A
R1C
R1B
K13
K14
AO
1
COM
AI1
+10
AI2
LI3
LI4
Fault
Manual
Speed
Potentiometer
(3)
L1
L3
F1
F2
(1)
Line
Reactor
L2
L2
F3
COM
LI1
LI2
+24
Start-Stop Push Buttons 
with Seal-in Relay
(6)
ST
OP
ST
AR
T
3
 P
h
as
e T
y
pe
 F
.ep
s
Notes
1. Line inductor, if required.
2. Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with 
the controller de-energized or faulted.
3. User-installed wiring for using LI2, LI3, and LI4 with internal +24 V power supply. When using a 
+24 V external supply, connect the 0 V to the COM terminal. Do not use the +24 terminal on the 
control board but connect logic inputs to external +24 V.
4. K13 and K14 are open terminals available for customer use.
5. See page 34 for the available braking resistor kits.
6. Manual speed potentiometer and start-stop push buttons are factory-installed in the enclosure 
cover. There is enough space in the cover to install one more 16-mm operator.