Recommended Branch Circuit Protection Devices
Branch circuit protection must be installed on the input (line side) of the drive controllers. Input fuses 
may be used on 1/2 hp to 500 hp drive controllers; circuit breakers may be used on 1/2 hp to 100 hp 
drive controllers.
Fuses
The fuses specified in Tables 1–3 (pages 113–114) are suitable for branch short circuit protection and 
provide excellent short circuit protection for the drive. Fuses are recommended for ATV58 TRX Type H 
and Type FVC drives when they are wall mounted.
Circuit Breakers
Circuit breakers will also provide branch short circuit protection. Because circuit breakers are typically 
slower than fuses, they are not as effective in limiting damage to the controller in the event of an internal 
drive short circuit such as shorted bus connections, shorted input rectifier, or failure of the internal solid 
state overcurrent protection circuit in the controller. Refer to the ALTIVAR 58 TRX Installation Guide for 
Type H Controllers (VVDED397048US) for recommended circuit breakers and application 
considerations.
 Table 1: Recommended Fuses: 208/230 V Single-Phase Drive Controllers
Motor
Drive Controller
F1-F2
Line Power Fuses
hp
kW
ATV58H•••••
Class J 
0.5
0.37
U09M2
10 
[1]
1
0.75
U18M2
15 
[1]
2
1.5
U29M2
30 
[1]
3
2.2
U41M2
30 
[1]
4
3
U72M2
35 
[1]
5
4
U90M2
60 
[1]
7.5
5.5
D12M2
70 
[1]
10
7.5
D16M2
90 
[2]
15
11
D23M2
125 
[2]
20
15
D28M2
150 
[2]
25
18.5
D33M2
175 
[2]
30
22
D46M2
200 
[2]
 Table 2: Recommended Fuses: 208/230 V Three-Phase Drive Controllers
Motor
Drive Controller
F1-F2-F3
Line Power Fuses
hp
kW
ATV58H•••••
Class J 
[1]
2
1.5
U29M2
15
3
2.2
U41M2
20
3
U54M2
30
5
4
U72M2
35
7.5
5.5
U90M2
60
10
7.5
D12M2
70
hp
kW
CTLN
ATV58H•••••
F1-F2-F3
Class J 
[2]
CT, VTLN
ATV58H••
•••
F1-F2-
F3
Class J 
[2]
VT
ATV58H••
•••
F1-F2-F3
Class J 
[2]
10
7.5
D16M2
70
15
11
D23M2
90
D16M2
70
D16M2
70
20
15
D28M2
110
D23M2
90
D16M2
90
25
18.5
D33M2
125
D28M2
110
D23M2
125
30
22
D46M2
175
D33M2
125
D28M2
150
40
30
D46M2
175
D33M2
175
50
37
D46M2
200
[1] Fast-acting or time 
delay Class J fuses are 
acceptable. Class T 
fuses are acceptable. 
Class CC fuses may be 
used if recommended 
fuse rating is 30 A or 
lower.
[2] Fast-acting Class J 
fuses. Class T fuses are 
acceptable.
[1] Fast-acting or time 
delay Class J fuses are 
acceptable. Class T 
fuses are acceptable. 
Class CC fuses may be 
used if recommended 
fuse rating is 30 A or 
lower.
[2] Fast-acting Class J 
fuses. Class T fuses are 
acceptable.
CT
Constant Torque
CTLN
Constant Torque Low 
Noise
VTLN
Variable Torque Low 
Noise
VT
Variable Torque